Operating Guide | VLT® Soft Starter MCD 600
12.2.26 Low Pressure
Cause
The pressure sensor connected to the smart card has activated low-pressure protection.
Troubleshooting
Check the following parameters:
-
Parameter 30-1 Pressure Sensor Type.
-
Parameter 30-3 Pressure at 4 mA.
-
Parameter 30-4 Pressure at 20 mA.
-
Parameter 32-4 Low Pressure Trip Level.
-
Parameter 32-5 Low Pressure Start Delay.
-
Parameter 32-6 Low Pressure Response Delay.
-
Parameter 36-5 Low Pressure.
12.2.27 Low Water
Cause
The depth sensor connected to the smart card has activated depth protection.
Troubleshooting
Check the following parameters:
-
Parameter 30-12 Depth Sensor Type.
-
Parameter 30-14 Depth at 4 mA.
-
Parameter 30-15 Depth at 20 mA.
-
Parameter 34-1 Depth Trip Level.
-
Parameter 34-2 Depth Reset Level.
-
Parameter 34-3 Depth Start Relay.
-
Parameter 36-9 Well Depth.
12.2.28 Motor Connection T1/T2/T3
Cause
This trip is not adjustable. The motor is not connected correctly to the soft starter.
Troubleshooting
Check individual motor connections to the soft starter for power circuit continuity.
Check connections at the motor terminal box.
If the soft starter is connected to a grounded delta mains supply, adjust parameter 20-6 Motor Connection to match the motor
connection configuration.
There are no parameters related to this trip message.
Danfoss A/S © 2018.10
Troubleshooting
AQ262141844215en-000202 / 175R1174 | 131