Operating Guide | VLT® Soft Starter MCD 600
12.2.26 Low Pressure
Cause
The pressure sensor connected to the smart card has activated low-pressure protection.
Troubleshooting
•
Check the following parameters:
-
Parameter 30-1 Pressure Sensor Type.
-
Parameter 30-3 Pressure at 4 mA.
-
Parameter 30-4 Pressure at 20 mA.
-
Parameter 32-4 Low Pressure Trip Level.
-
Parameter 32-5 Low Pressure Start Delay.
-
Parameter 32-6 Low Pressure Response Delay.
-
Parameter 36-5 Low Pressure.
12.2.27 Low Water
Cause
The depth sensor connected to the smart card has activated depth protection.
Troubleshooting
•
Check the following parameters:
-
Parameter 30-12 Depth Sensor Type.
-
Parameter 30-14 Depth at 4 mA.
-
Parameter 30-15 Depth at 20 mA.
-
Parameter 34-1 Depth Trip Level.
-
Parameter 34-2 Depth Reset Level.
-
Parameter 34-3 Depth Start Relay.
-
Parameter 36-9 Well Depth.
12.2.28 Motor Connection T1/T2/T3
Cause
This trip is not adjustable. The motor is not connected correctly to the soft starter.
Troubleshooting
•
Check individual motor connections to the soft starter for power circuit continuity.
•
Check connections at the motor terminal box.
•
If the soft starter is connected to a grounded delta mains supply, adjust parameter 20-6 Motor Connection to match the motor
connection configuration.
•
There are no parameters related to this trip message.
Danfoss A/S © 2018.10
Troubleshooting
AQ262141844215en-000202 / 175R1174 | 131