Operating Guide | VLT® Soft Starter MCD 600
If the installation requires large diameter cables, it is possible to complete each termination with 2 smaller cables, 1 on each
side of the busbar.

5.7.1 Wiring Connectors

Select a connector according to the wire size, material, and application requirements.
For models MCD6-0144B to MCD6-0579B, a compression connector is recommended. The recommended crimping tool is TBM8-750.
Table 15: Recommended Lugs
Model
Example connector - aluminum cable
MCD6-0144B
61162
MCD6-0171B
61165
MCD6-0194B
61171
MCD6-0244B
MCD6-0287B
61162
MCD6-0352B
61165
MCD6-0410B
MCD6-0527B
61178
MCD6-0579B

5.7.2 Motor Connection

The VLT® Soft Starter MCD 600 can be connected to the motor in-line or inside delta (also called 3-wire and 6-wire connection). When
connecting in inside delta, enter the FLC for parameter 1-2 Motor Full Load Current. The MCD 600 automatically detects whether the
motor is connected in-line or inside delta and calculates the correct inside delta current level.
If the soft starter is not detecting the motor connection correctly, use parameter 20-6 Motor Connection.
34 | Danfoss A/S © 2018.10
N O T I C E
Example connector - copper cable
60150
60156
60165
60150
60156
60156
60171
N O T I C E
Installation
AQ262141844215en-000202 / 175R1174