REDUCED EQUIPMENT LIFETIME
Continued use of emergency mode is not recommended. Emergency mode may compromise the soft starter and/or motor life
as all protections and trips are disabled. Using the soft starter in emergency mode voids the product warranty.
Do not run the soft starter in emergency mode continuously.
-

9.6 Auxiliary Trip

An external trip circuit (such as a low-pressure alarm switch for a pumping system) can be used to trip the soft starter and stop the
motor. The external circuit is connected to a programmable input (input A DI-A, COM+ or input B DI-B, COM+). To control the behavior
of the trip, set the following parameters:
Parameter 7-1 Input A Function: Select Input Trip (N/O).
Parameter 7-2 Input A Trip: Set as required. For example, Run Only limits the input trip to when the soft starter is running only.
Parameter 7-3 Input A Trip Delay: Sets a delay between the input activating and the soft starter tripping.
Parameter 7-4 Input A Initial Delay: Sets a delay before the soft starter monitors the state of the input after the start signal. For
example, a delay may be required to allow time for pipeline pressure to build up.
Parameter 7-10 Input A Name: Select a name, for example Input A Trip (optional).

9.7 Typical Control Methods

The requirements for an application differ between each installation, but the methods listed below are often a good starting point for
common applications.
Table 18: Typical Control Methods
Application
Bow thruster
Centrifuge (separator)
Chipper
Compressor - reciprocat-
ing - loaded
Compressor - reciprocat-
ing - unloaded
Compressor - screw - loa-
ded
Compressor - screw -. un-
loaded
Conveyor - horizontal
Conveyor - inclined
Conveyor - vertical (buck-
et)
56 | Danfoss A/S © 2018.10
Start mode
Start
ramp
time [s]
Constant current
5
Constant current
1
Constant current
1
Constant current
1
Constant current
1
Constant current
1
Constant current
1
Constant current
5
Constant current
2
Constant current
2
N O T I C E
Initial cur-
Current
rent
limit
(%FLC)
(%FLC)
100
400
200
450
200
450
200
450
200
400
200
400
200
350
200
400
200
450
200
450
Operation
Stop mode
Stop time
[s]
Coast to stop
n/a
Coast to stop
n/a
Coast to stop
n/a
Coast to stop
n/a
Coast to stop
n/a
Coast to stop
n/a
Coast to stop
n/a
TVR soft stop
10
Coast to stop
n/a
Coast to stop
n/a
AQ262141844215en-000202 / 175R1174