Operating Guide | VLT® Soft Starter MCD 600
Table 57: 3-13 - Adaptive Stop Profile-2
Option
Early Deceleration
*
Constant Deceleration
Late Deceleration
Table 58: 3-14 - Adaptive Control Gain-2
Range
*75%
1–200%
Table 59: 3-15 - Multi Pump-2
Option
Function
Adjusts the performance of adaptive control to suit installations with multiple pumps connected to a com-
mon outlet manifold.
*
Single Pump
Manifold Pump
Table 60: 3-16 - Start Delay-2
Range
* 0 s
0:00–60:00 (minutes:seconds)
Table 61: 3-17 - DC Brake Torque-2
Range
*20%
20–100%
Table 62: 3-18 - DC Brake Time-2
Range
*1 s
0:01–0:30 (minutes:seconds)
Table 63: 3-19 - Brake Current Limit-2
Range
*250%
100–600% FLC
84 | Danfoss A/S © 2018.10
Function
Selects which profile the soft starter uses for an adaptive control soft stop.
Function
Adjusts the performance of adaptive control.
This setting affects both starting and stopping control.
Function
Sets a delay after the starter receives a start command before it starts the motor.
Function
Sets the amount of brake torque the soft starter uses to slow the motor.
Function
Sets the duration for DC injection during a braking stop.
Function
Sets the current limit for soft brake.
Programmable Parameters