Danfoss VLT MCD 600 Operating Manual

Danfoss VLT MCD 600 Operating Manual

Hide thumbs Also See for VLT MCD 600:
Table of Contents

Advertisement

Operating Guide
VLT® Soft Starter MCD 600

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT MCD 600 and is the answer not in the manual?

Questions and answers

Summary of Contents for Danfoss VLT MCD 600

  • Page 1 Operating Guide VLT® Soft Starter MCD 600...
  • Page 3: Table Of Contents

    3.13 UL Coordination with Short-circuit Protection Devices 3.13.1 Standard Fault Short-circuit Current Ratings 3.13.2 High Fault Short-circuit Current Ratings 3.14 Fuse Selection for Type 2 Coordination 4 Specifications Supply Short-circuit Capability Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 3...
  • Page 4 Power Terminations 5.7.1 Wiring Connectors 5.7.2 Motor Connection 5.7.2.1 In-line Installation 5.7.2.2 Inside Delta Installation Typical Installation Quick Set-up 6 Set-up Tools Introduction Setting Date and Time Command Source Commissioning Run Simulation 4 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 5 Performance Graph 9 Operation Start, Stop, and Reset Commands Command Override Auto-start/Stop 9.3.1 Clock Mode 9.3.2 Timer Mode PowerThrough Emergency Mode Auxiliary Trip Typical Control Methods Soft Start Methods 9.8.1 Constant Current Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 5...
  • Page 6 10.20 Parameter Group 32-** Pressure Protection 10.21 Parameter Group 33-** Pressure Control 10.22 Parameter Group 34-** Depth Protection 10.23 Parameter Group 35-** Thermal Protection 10.24 Parameter Group 36-** Pump Trip Action 6 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 7 Smart Card - Pump Control and Protection 11.2 Smart Card - Level-controlled Pump Activation 12 Troubleshooting 12.1 Protection Responses 12.2 Trip Messages 12.3 General Faults 13 Appendix 13.1 Symbols and Abbreviations 13.2 Conventions Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 7...
  • Page 8: Introduction

    Installation guides for installing various accessories. • WinStart Design Tool to help with selecting the right soft starter for an application. Supplementary publications and manuals are available from www.danfoss.com/en/search/?filter=type%3Adocumentation. 1.4 Approvals and Certifications 8 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 9: Safety

    N O T I C E The VLT® Soft Starter MCD 600 is not user serviceable. The unit should only be serviced by authorized service personnel. Unauthorized tampering with the unit voids the product warranty. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 9...
  • Page 10 The motor could restart after the causes of a shutdown are rectified, which may be dangerous for certain machines or installations. Ensure that appropriate arrangements are made against restarting after unscheduled stops of the motor. 10 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 11 Responsibility or liability is never accepted for direct, indirect, or consequential damage resulting from the use or application of this equipment. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 11...
  • Page 12: System Design

    • Adaptive control. • Constant current. • Current ramp. • Pump clean. • Timed voltage ramp soft stop. • Coast to stop. • DC brake. • Soft brake. • Reverse direction. 12 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 13: Type Code

    S1X = Frame size 1 S2X = Frame size 2 Mains voltage T5 = 200~525 V AC T7 = 380~690 V AC Bypass B = Internally bypassed Nominal current rating Illustration 1: Type Code String Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 13...
  • Page 14: Selection Of Soft Starter Size

    All ratings are calculated at an altitude of 1000 m (3280 ft) and an ambient temperature of 40 °C (104 °F). Table 2: In-line Installation, MCD6-0020B ~ MCD6-0042B 3.0-10:350 3.5-15:345 4.0-10:350 4.0-20:340 5.0-5:355 MCD6-0020B MCD6-0034B MCD6-0042B Table 3: In-line Installation, MCD6-0063B ~ MCD6-0579B 3.0-10:590 3.5-15:585 4.0-10:590 4.0-20:580 5.0-5:595 MCD6-0063B MCD6-0069B MCD6-0086B 14 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 15 Table 4: Inside Delta Installation 3.0-10:350 3.5-15:345 4.0-10:350 4.0-20:340 5.0-5:355 MCD6-0020B MCD6-0034B MCD6-0042B 3.0-10:590 3.5-15:585 4.0-10:590 4.0-20:580 5.0-5:595 MCD6-0063B MCD6-0069B MCD6-0086B MCD6-0108B MCD6-0129B MCD6-0144B MCD6-0171B MCD6-0194B MCD6-0244B MCD6-0287B MCD6-0323B MCD6-0410B MCD6-0527B MCD6-0579B Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 15...
  • Page 16: Dimensions And Weight

    5.5 (12.1) MCD6-0108B MCD6-0129B MCD6-0144B 216 (8.5) 180 (7.1) 495 (19.5) 450 (17.7) 243 (9.6) 12.7 (28) MCD6-0171B MCD6-0194B MCD6-0244B 15.5 (34.2) MCD6-0287B 523 (20.6) MCD6-0323B MCD6-0410B MCD6-0527B 19 (41.9) MCD6-0579B 16 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 17: Physical Installation/Cooling Clearances

    The smart card has been designed to support integration with pumping applications and provides the following additional inputs and outputs: • 3 x digital inputs. • 3 x 4–20 mA transducer inputs. • 1 x RTD input. • 1 x USB-B port. • Remote LCP connector. Ordering number: 175G0133 Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 17...
  • Page 18: Communication Expansion Cards

    Load Procedure. The VLT® Motion Control Tool MCT 10 can help manage the soft starter. Contact the local supplier for more information. Documentation for the VLT® Motion Control Tool MCT 10 can be downloaded from www.danfoss.com/en/search/?filter=type %3Adocumentation. 3.8 Main Contactor A main contactor is recommended to protect the soft starter from voltage disturbances on the network while stopped.
  • Page 19: Circuit Breaker

    Connecting power factor correction capacitors to the output side damages the soft starter. Always connect power factor correction capacitors to the input side of the soft starter. Do not use the soft starter relay output to switch in power factor correction directly. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 19...
  • Page 20: Short-Circuit Protection Devices

    Type 1 coordination 480 V AC, 65 kA Type 2 coordination 690 V AC, SCR I t (A Bussmann NH fuse links 65 kA Bussmann DIN 43 653 MCD6-0020B 1150 40NHG000B 170M3010 20 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 21: Ul Coordination With Short-Circuit Protection Devices

    Table 9: Maximum Fuse Rating [A] - Standard Fault Short-Circuit Current Model Nominal rating [A] 3 cycle short cct rating @600 V AC MCD6-0020B 5 kA MCD6-0034B MCD6-0042B 10 kA MCD6-0063B MCD6-0069B MCD6-0086B MCD6-0108B MCD6-0129B Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 21...
  • Page 22: High Fault Short-Circuit Current Ratings

    MCD6-0579B Suitable for use on a circuit capable of delivering not more than 65000 rms symmetrical amperes, 480 V AC maximum, when protected by fuses of the stated class and rating. 22 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 23: Fuse Selection For Type 2 Coordination

    For further information on selecting semiconductor fuses, contact the local distributor. Table 12: SCR Values for Semiconductor Fuses Model SCR I t [A MCD6-0020B 1150 MCD6-0034B 7200 MCD6-0042B MCD6-0063B 15000 MCD6-0069B Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 23...
  • Page 24 Operating Guide | VLT® Soft Starter MCD 600 System Design Model SCR I t [A MCD6-0086B 80000 MCD6-0108B MCD6-0129B 125000 MCD6-0144B 320000 MCD6-0171B MCD6-0194B MCD6-0244B MCD6-0287B 202000 MCD6-0323B MCD6-0410B 320000 MCD6-0527B 781000 MCD6-0579B 24 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 25: Specifications

    Normally open Relay output A (21, 22, 23) Changeover Relay output B (33, 34) Normally open Analog output (AO-07, AO-08) Maximum load 600 Ω (12 V DC @ 20 mA) Accuracy ±5% Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 25...
  • Page 26: Environmental

    Class 10, trip current 105% of FLA (full load amperage) or protection. equivalent 4.9 Certification EN 60947-4-2 UL/C-UL UL 508 Marine Lloyds Marine No 1 specification 4.10 Operational Life (Internal Bypass Contacts) Expected operational lifetime 100000 operations 26 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 27: Installation

    Set up the command source via Set-up Tools or via parameter 1-1 Command Source. If the remote LCP is installed, the [CMD/Menu] key provides shortcut access to the Command Source function in Set-up Tools. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 27...
  • Page 28: Setting Up The Soft Starter

    The control inputs are powered by the soft starter. Do not apply external voltage to the control input terminals. N O T I C E Cables to the control inputs must be segregated from mains voltage and motor cabling. 28 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 29: Input Terminals

    MCD 600 but are no longer required, use the Thermistor Reset function to disable the thermistor. Thermistor reset is accessed via Set-up Tools. 5.4.3 Start/Stop The VLT® Soft Starter MCD 600 requires 2-wire control. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 29...
  • Page 30: Reset/Starter Disable

    The USB port can be used to upload a configuration file, or download parameter settings and event log information from the soft starter. See 6.7 USB Save & Load for details. 30 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 31: Outputs

    N O T I C E Some electronic contactor coils are not suitable for direct switching with PCB mount relays. Consult the contactor manufacturer/supplier to confirm suitability. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 31...
  • Page 32: Programmable Outputs

    For MCD6-0144B to MCD6-0579B to be UL-compliant, supplementary or branch circuit overcurrent protection must be used on the control circuit supply (A7, A8, A9) in accordance with the electrical code applicable at the installation location. 32 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 33: Power Terminations

    MCD6-0287B~MCD6-0579B 19 Nm (14 ft-lb) 66 Nm (49 ft-lb) 13 mm (M12) 9 mm (M8) 20 mm 34 mm 6 mm 6 mm 0.8 in 1.7 in 0.24 in 0.24 in Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 33...
  • Page 34: Wiring Connectors

    N O T I C E If the soft starter is not detecting the motor connection correctly, use parameter 20-6 Motor Connection. 34 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 35: In-Line Installation

    Illustration 10: Wiring of an In-line Installation 5.7.2.2 Inside Delta Installation 1/L1 2/T1 U1(1) U2(4) 3/L2 4/T2 V1(2) V2(5) W1(3) W2(6) 5/L3 6/T3 K1 Main contactor F1 Fuses or circuit breaker (optional Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 35...
  • Page 36: Typical Installation

    2/T1 3/L2 4/T2 5/L3 6/T3 (L/+) (N/# ) RESET COM+ START COM+ DI-A DI-B AO-07 TER-05 TER-06 AO-08 1 Three-phase supply 2 Motor 3 Control voltage (soft starter) 4 Digital inputs 36 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 37: Quick Set-Up

    Fan undamped Constant cur- Coast to stop rent Compressor Constant cur- Coast to stop screw rent Compressor re- Constant cur- Coast to stop rent Conveyor Constant cur- Coast to stop rent Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 37...
  • Page 38 N O T I C E The adaptive start and stop profile settings only apply when using adaptive control. The settings are ignored for all other start and stop modes. 38 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 39: Set-Up Tools

    The Run Simulation simulates a motor starting, running, and stopping to confirm that the soft starter and associated equipment have been installed correctly. N O T I C E Disconnect the soft starter from mains voltage when using simulation mode. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 39...
  • Page 40: Load/Save Settings

    Resetting the soft starter parameters to default values. • Loading parameter settings from an internal file. • Saving the current parameter settings to an internal file. The internal file contains default values until a user file is saved. 40 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 41: Usb Save & Load

    Loading custom messages to show on the LCP when a programmable input is active. N O T I C E The VLT® Soft Starter MCD 600 supports FAT32 file systems. The MCD 600 USB functions are not compatible with NTFS file systems. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 41...
  • Page 42: Save And Load Procedure

    Load master parameters The soft starter loads the file Master_Parameters.par from the top level of the USB drive. The files can be created or edited using VLT® Motion Control Tool MCT 10. Download the MCT 10 tool from www.danfoss.com/en/service-and-support/downloads/dds/vlt-motion- control-tool-mct-10/.
  • Page 43: Auto-Start/Stop

    Press [Menu/Store] to save changes. The soft starter confirms the changes. Press [Back] to cancel the changes. 6.9 Network Address To use the VLT® Soft Starter MCD 600 on an Ethernet network, separate addresses must be configured for: Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 43...
  • Page 44: Setting A Network Address

    To configure the soft starter for use with other communication protocols, use parameters 12-1 to 12-7. 6.10 Digital I/O State Digital I/O State Inputs: 0100 Outputs: 100 Illustration 14: Digital I/O Status Screen 44 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 45: Analog I/O State

    Analog I/O Status Screen Thermistor input Short Cold Open 6.12 Serial Number & Rating The top line of the screen shows the product name. The middle line shows the unit's serial number. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 45...
  • Page 46: Software Versions

    N O T I C E REDUCED MOTOR LIFETIME Resetting the motor thermal model compromises thermal model protection and may compromise motor life. Only reset the thermal model in an emergency. 46 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 47: Logs

    5. To reset a counter, press [Menu/Store] then press [▵] and [▿] to select Reset/Do Not Reset. 6. Press [Store] to confirm the action. 7. Press [Menu/Store] to close the counter and return to Logs. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 47...
  • Page 48: Lcp And Feedback

    Illustration 18: Local LCP 8.2 Remote LCP The remote LCP can be used to control the soft starter if parameter 1-1 Command Source is set to Remote Keypad. 48 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 49 Graph: Select Tools: for quick Open the which graph to Open the access to Logs view, or pause/ Set-up common tasks: Menu. restart the graph Tools. (hold longer than 0.5 s). Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 49...
  • Page 50: Adjusting The Display Contrast

    The thermal models indicate that the soft starter and/or motor are too hot to start safely. • The reset input (RESET, COM+) is open. The motor is in run state (receiving full The motor is starting or stopping. voltage). 50 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 51: Displays

    Running 69.0 A 415 V 1 Motor running current 2 Soft starter status 3 Parameter 10-8 User Parameter 1 and parameter 10-9 User Parameter 2 Illustration 22: Soft Starter Status Screen Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 51...
  • Page 52: Operating Feedback Screens

    8.5.4 Performance Graph The performance graph provides a real-time display of operating performance. Use parameters 10-2 to 10-5 to format the graph. The display on the main LCP shows information for motor current. 52 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 53 If a remote LCP is connected, press [Graph] to change the graph data. The graph can show: • Motor current. • Motor temperature. • Motor power factor. • Analog input data from the smart card (if installed). Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 53...
  • Page 54: Operation

    The soft starter can automatically stop the motor after a specified run-time, then restart it after a specified off (stopped) time. The soft starter repeats the cycle while the start signal remains active. For timer mode to operate: 54 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 55: Powerthrough

    Emergency mode can be used with any command source. N O T I C E Although emergency mode operation satisfies the functionality requirements of fire mode, Danfoss does not recommend its use in situations that require testing and/or compliance with specific standards as it is not certified.
  • Page 56: Auxiliary Trip

    Constant current Coast to stop loaded Conveyor - horizontal Constant current TVR soft stop Conveyor - inclined Constant current Coast to stop Conveyor - vertical (buck- Constant current Coast to stop 56 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 57: Soft Start Methods

    Constant current is the traditional form of soft starting, which raises the current from 0 to a specified level and keeps the current stable at that level until the motor has accelerated. Constant current starting is ideal for applications where the start current must be kept below a particular level. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 57...
  • Page 58: Constant Current With Current Ramp

    The load breaks away easily, but starting time has to be extended (for example a centrifugal pump where pipeline pressure has to build up slowly). • The electricity supply is limited (for example a generator set), and a slower application of load allows greater time for the supply to respond. 58 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 59: Adaptive Control For Starting

    (set in parameter 2-2 Start Ramp Time) is too short, the motor may not start successfully. Time 1 Early acceleration 2 Constant acceleration 3 Late acceleration 4 Parameter 2-2 Start Ramp Time Illustration 28: Example of Adaptive Control Start (Parameter 2-5 Adaptive Start Profile) Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 59...
  • Page 60: Fine-Tuning Adaptive Control

    2 Parameter 2-6 Kickstart Time 3 Parameter 2-3 Initial Current 4 Parameter 2-2 Start Ramp Time 5 Parameter 2-4 Current Limit 6 Full voltage current Illustration 29: Example of Kickstart used with Constant Current 60 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 61: Stop Methods

    Adaptive control does not actively slow the motor down and does not stop the motor faster than a coast to stop. To shorten the stopping time of high inertia loads, use brake. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 61...
  • Page 62: Dc Brake

    During braking, an increased noise level from the motor may be audible. This is a normal part of motor braking. N O T I C E When using DC brake, the mains supply must be connected to the soft starter (input terminals L1, L2, and L3) in positive phase sequence. 62 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 63 • Parameter 2-16 DC Brake Time: Set this parameter to approximately 1 quarter of the programmed stop time. This sets the time for the full brake stage (2). Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 63...
  • Page 64: Dc Brake With External Zero-Speed Sensor

    Set to allow time for K1 and K2 to switch. • Parameter 7-1 Input A Function: Set to Zero Speed Sensor. • Parameter 8-1 Relay A Function: Set to Soft Brake Relay. 64 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 65: Pump Clean

    7-1 Input A Function for details). Ensure that the input is closed when the start signal is applied. N O T I C E Do not enable pump clean on pumps that cannot operate in reverse direction. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 65...
  • Page 66: Reverse Direction Operation

    The first start after the direction is changed will be constant current. N O T I C E If phase sequence protection is required, install the reversing contactor on the output (motor) side of the soft starter. 66 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 67: Jog Operation

    Slow speed running is not intended for continuous operation due to reduced motor cooling. Jog operation causes the motor to heat faster than the rate calculated by the motor thermal model. Install a motor thermistor or allow sufficient restart delay (parameter 5-16 Restart Delay). Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 67...
  • Page 68: Inside Delta Operation

    Adaptive control, jog, brake, and PowerThrough functions are not supported with inside delta (6-wire) operation. If these functions are programmed when the soft starter is connected inside delta, the behavior is given as below. 68 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 69: Secondary Motor Set

    The soft starter uses the secondary motor settings to control a start when instructed via a programmable input (see parameter 7-1 Input A Function and parameter 7-5 Input B Function). N O T I C E The motor thermal model is less accurate if the soft starter controls 2 separate motors. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 69...
  • Page 70: Programmable Parameters

    Model dependent Motor kW 0 kW Locked Rotor Time 00:10 (mm:ss) Locked Rotor Current 600% Motor Service Factor 105% Reserved – Motor Start/Stop Start Mode Constant Current Start Ramp Time 00:10 (mm:ss) 70 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 71 00:00 (mm:ss) 3-13 Adaptive Stop Profile-2 Constant Deceleration 3-14 Adaptive Control Gain-2 3-15 Multi Pump-2 Single Pump 3-16 Start Delay-2 00:00 (mm:ss) 3-17 DC Brake Torque-2 3-18 DC Brake Time-2 00:01 (mm:ss) Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 71...
  • Page 72 00:00 (hh:mm) 4-24 Saturday Stop Time 00:00 (hh:mm) Protection Levels Current Imbalance Current Imbalance Delay 00:03 (mm:ss) Undercurrent Undercurrent Delay 00:05 (mm:ss) Overcurrent 400% Overcurrent Delay 00:00 (mm:ss) Undervoltage 350 V 72 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 73 Motor Thermistor Circuit Soft Trip and Log 6-19 Shorted SCR Action 3-Phase Control Only 6-20 Battery/Clock Soft Trip and Log Inputs Input A Function Input Trip (N/O) Input A Trip Operating Only Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 73...
  • Page 74 30 s 10-4 Graph Maximum Adjustment 400% 10-5 Graph Minimum Adjustment 10-6 Current Calibration 100% 10-7 Adjustment Lock Read & Write 10-8 User Parameter 1 Current 10-9 User Parameter 2 Motor Voltage 74 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 75 IP Address 2 12-14 IP Address 3 12-15 IP Address 4 12-16 Subnet Mask 12-17 Subnet Mask 2 12-18 Subnet Mask 3 12-19 Subnet Mask 4 12-20 DHCP Disable 12-21 Location ID Advanced Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 75...
  • Page 76 High Pressure Start Delay 00:00:500 (mm:ss:ms) 32-3 High Pressure Response Delay 00:00:500 (mm:ss:ms) 32-4 Low Pressure Trip Level 32-5 Low Pressure Start Delay 00:00:500 (mm:ss:ms) 32-6 Low Pressure Response Delay 00:00:500 (mm:ss:ms) Pressure Control 76 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 77: Parameter Group 1-** Motor Details

    The soft starter accepts start and stop commands from the remote LCP. Clock The soft starter accepts starts and stops as scheduled in parameters 4-1 to 4-24. Smart card The soft starter accepts start and stop commands from the smart card. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 77...
  • Page 78 1-4 to 1-6 provide motor overload protection: Class 10, trip current 105% of FLA (full load amperage) or equivalent. Table 26: 1-7 Reserved Range Function This parameter is reserved for future use. 78 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 79: Parameter Group 2-** Motor Start/Stop

    The MCD 600 applies the current limit on all soft starts, including adaptive control. If the cur- rent limit is too low or the start ramp time (parameter 2-2 Start Ramp Time) is too short, the motor may not start successfully. Early Acceleration Constant Acceleration Late Acceleration Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 79...
  • Page 80 14) to control the main contactor. Table 37: 2-11 - Adaptive Stop Profile Option Function Selects which profile the VLT® Soft Starter MCD 600 uses for an adaptive control soft stop. Early Deceleration Constant Deceleration 80 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 81: Parameter Group 3-** Motor Start/Stop-2

    10.7 Parameter Group 3-** Motor Start/Stop-2 The parameters in this group control the operation of the secondary configuration of the motor. Use the programmable input to select the active motor set. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 81...
  • Page 82 The VLT® Soft Starter MCD 600 applies the current limit on all soft starts, including adaptive control. If the current limit is too low or the start ramp time (parameter 2-2 Start Ramp Time) is too short, the motor may not start successfully. 82 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 83 Sets the time for soft stopping the motor using TVR or adaptive control. If a main contactor is installed, nutes:seconds) the contactor must remain closed until the end of the stop time. Use the main contactor output (13, 14) to control the main contactor. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 83...
  • Page 84 0:01–0:30 (minutes:seconds) Sets the duration for DC injection during a braking stop. Table 63: 3-19 - Brake Current Limit-2 Range Function *250% 100–600% FLC Sets the current limit for soft brake. 84 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 85: Parameter Group 4-** Auto-Start/Stop

    Range Function *00:00 00:00–23:59 Sets the auto-start time for Sunday (24-hour format). Table 70: 4-6 - Sunday Stop Time Range Function *00:00 00:00–23:59 Sets the auto-stop time for Sunday (24-hour format). Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 85...
  • Page 86 Enables or disables auto-start/stop for Wednesday. Start/Stop Disable Start Only Enable Stop Only Enable Start/Stop Enable Table 77: 4-14 - Wednesday Start Time Range Function *00:00 00:00–23:59 Sets the auto-start time for Wednesday (24-hour format). 86 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 87 Range Function *00:00 00:00–23:59 Sets the auto-start time for Friday (24-hour format). Table 84: 4-21 - Friday Stop Time Range Function *00:00 00:00–23:59 Sets the auto-stop time for Friday (24-hour format). Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 87...
  • Page 88: Parameter Group 5-** Protection Levels

    0% disables undercurrent protection. Table 91: 5-4 - Undercurrent Delay Range Function * 5 s 00–4:00 (minutes:seconds) Slows the soft starter's response to undercurrent, avoiding trips due to momentary fluctua- tions. 88 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 89 Sets the trip point for underpower protection. Set as required. Table 99: 5-12 - Underpower Delay Range Function *1 s 0:00–1:00 (minutes:seconds) Slows the soft starter's response to underpower, avoiding trips due to momentary fluctua- tions. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 89...
  • Page 90 When using DC brake, the mains supply must be connected to the soft starter (input terminals L1, L2, L3) in positive phase sequence. Parameter 2-1 Phase Sequence must be set to Positive Only. 90 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 91: Parameter Group 6-** Protection Action

    Table 109: 6-4 - Undercurrent Option Function Selects the soft starter's response to the protection event. Soft Trip and Log Soft Trip and Reset Trip Starter Trip and Reset Warn and Log Log Only Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 91...
  • Page 92 Warn and Log Log Only Table 113: 6-8 - Underpower Option Function Selects the soft starter's response to the protection event. Soft Trip and Log Soft Trip and Reset Trip Starter 92 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 93 Table 116: 6-11 - Input A Trip Option Function Selects the soft starter's response to the protection event. Soft Trip and Log Soft Trip and Reset Trip Starter Trip and Reset Warn and Log Log Only Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 93...
  • Page 94 Soft Trip and Reset Trip Starter Trip and Reset Warn and Log Log Only Table 120: 6-15 - Frequency Option Function Selects the soft starter's response to the protection event. Soft Trip and Log 94 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 95 Table 123: 6R - Motor Thermistor Circuit Option Function Selects the soft starter's response to the protection event. Soft Trip and Log Soft Trip and Reset Trip Starter Trip and Reset Warn and Log Log Only Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 95...
  • Page 96: Parameter Group 7-** Inputs

    Activates jog operation in reverse direction. Zero Speed Sensor An open circuit across DI-A, COM+ indicates to the soft starter that the motor has reached a standstill. The soft starter requires a normally open zero-speed sensor. 96 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 97 Selects the function of Input B. See parameter 7-1 Input A Function for details. Input Trip (N/O) Input Trip (N/C) Emergency Mode Jog Forward Jog Reverse Zero Speed Sensor Motor Set Select Reverse Direction Pump Clean Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 97...
  • Page 98 Selects a message for the LCP to show when Input A is active. The custom message can be loaded via the USB port. Input A Trip Low Pressure High Pressure Pump Fault Low Level High Level No Flow 98 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 99 Input B Trip Low Pressure High Pressure Pump Fault Low Level High Level No Flow Starter Disable Controller Vibration Alarm Field Trip Interlock Trip Motor Temp Motor Prot Feeder Prot Custom Message Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 99...
  • Page 100: Parameter Group 8-** Relay Outputs

    Sets the delay for changing the state of Relay A. Table 140: 8-4 - Relay B Function Option Function Selects the function of Relay B (normally open). See parameter 8-1 Relay A Function for details. Ready Warning 100 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 101 1 of the programmable outputs. Set the level at which the motor temperature flag operates as a percentage of the motor's thermal capacity. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 101...
  • Page 102: Parameter Group 9-** Analog Output

    Calibrates the lower limit of the analog output to match the signal measured on an external current measuring device. 10.14 Parameter Group 10-** Display Table 151: 10-1 - Language Option Function Selects in which language the LCP shows messages and feedback. 102 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 103 Range Function * 400% 0–600% Adjusts the upper limit of the performance graph. Table 155: 10-5 - Graph Minimum Adjustment Range Function 0–600% Adjusts the lower limit of the performance graph. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 103...
  • Page 104 The pump temperature, as measured by the PT100. This information is only available if the smart card is installed. Analog Output Value The value of the analog output (see parameter group 9-** Analog Output). 104 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 105 Option Function Selects which information is shown on the programmable monitoring screen. See parameter 10-8 User Parameter 1 for details. Motor Temp (%) See parameter 10-8 User Parameter 1 for details. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 105...
  • Page 106: Parameter Group 11-** Pump Clean

    Sets how many times the soft starter repeats the pump clean cycle. 10.16 Parameter Group 12-** Communication Card Table 171: 12 A - Modbus Address Range Function 1–254 Sets the Modbus RTU network address for the soft starter. 106 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 107 Sets the DeviceNet network address for the soft starter. Table 176: 12-6 - Devicenet Baud Rate Option Function Selects the baud rate for DeviceNet communications. 125 kB 250 kB 500 kB Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 107...
  • Page 108 IP address for Ethernet communications. Table 184: 12-14 - IP Address 3 Range Function 0–255 Sets the 3 component of the soft starter's IP address for Ethernet communications. 108 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 109 Selects whether the communications card accepts an IP address assigned by DHCP. Disable Enable N O T I C E DHCP addressing is available with Modbus TCP and EtherNet/IP. DHCP addressing is not supported with PRO- FINET. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 109...
  • Page 110: Parameter Group 20-** Advanced

    This parameter can only be adjusted by authorized servicing agents. Table 196: 20-5 - Screen Timeout Option Function Sets the timeout for the menu to close automatically if no LCP activity is detected. 1 minute 110 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 111: Parameter Group 30-** Pump Input Configuration

    Calibrates the soft starter to the 4 mA (0%) level of the pressure sensor input. Table 201: 30-4 - Pressure at 20 mA Range Function 0–5000 Calibrates the soft starter to the 20 mA (100%) level of the pressure sensor input. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 111...
  • Page 112 Calibrates the soft starter to the maximum flow volume of the flow sensor. Table 208: 30-11 - Units per Pulse Range Function 0–1000 Set to match how many units the flow sensor measures for each pulse. 112 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 113: Parameter Group 31-** Flow Protection

    Table 213: 31-1 - High Flow Trip Level Range Function 0–5000 Sets the trip point for high flow protection. Table 214: 31-2 - Low Flow Trip Level Range Function 1–5000 Sets the trip point for low flow protection. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 113...
  • Page 114: Parameter Group 32-** Pressure Protection

    Sets a delay between the pressure passing the high-pressure trip level and the soft starter trip- mm:ss:ms ping. Table 220: 32-4 - Low Pressure Trip Level Range Function 0–5000 Sets the trip point for low-pressure protection. 114 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 115: Parameter Group 33-** Pressure Control

    Sets a delay between the pressure passing the pressure control start level and the soft starter per- mm:ss:ms forming a soft start. Table 226: 33-4 - Stop Pressure Level Range Function * 10 0–5000 Sets the pressure level to trigger the soft starter to stop the motor. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 115...
  • Page 116: Parameter Group 34-** Depth Protection

    Sets a delay between the depth passing the depth protection trip level and the soft starter trip- mm:ss:ms ping. 10.23 Parameter Group 35-** Thermal Protection N O T I C E The parameters in this group are only active if a smart card is installed. 116 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 117: Parameter Group 36-** Pump Trip Action

    Warn and Log Log Only Table 236: 36-3 - Depth Sensor Option Function Selects the soft starter's response if it detects a fault with the depth sensor. Soft Trip and Log Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 117...
  • Page 118 Selects the soft starter's response if the flow exceeds the high flow trip level (parameter 31-1 High Flow Trip Level). Soft Trip and Log Soft Trip and Reset Trip Starter Trip and Reset Warn and Log 118 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 119 Selects the soft starter's response if the depth drops below the depth trip level (parameter 34-1 Depth Trip Level) or the depth switch sensor closes. Soft Trip and Log Soft Trip and Reset Trip Starter Trip and Reset Warn and Log Log Only Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 119...
  • Page 120 Table 243: 36-10 - RTD/PT100 B Option Function Selects the soft starter's response to the protection event. Soft Trip and Log Soft Trip and Reset Trip Starter Trip and Reset Warn and Log Log Only 120 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 121: Application Examples

    1 Digital inputs 2 Control voltage 3 Three-phase supply 4 Smart card 5 Remote LCP (optional) 6 Pressure sensor 7 Flow sensor 8 Depth sensor 9 Temperature sensor A Manual start Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 121...
  • Page 122: Smart Card - Level-Controlled Pump Activation

    When the water drops below the minimum level, the soft starter triggers the pump to fill the tank and shuts off the pump when the maximum water level is reached. A 3-way selector switch allows overriding sensor-based control and manually start and stop the motor. 122 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 123 • Parameters 30-1 to 30-15 Pump Input Configuration: Set as required. • Parameter 31-1 to 31-4 Flow Protection: Set as required. • Parameter 33-1 to 33-5 Pressure Control: Set as required. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 123...
  • Page 124: Troubleshooting

    This trip is not adjustable. Bypass overload protection protects the soft starter from severe operating overloads while running. The soft starter trips if it detects overcurrent at 600% of the contactor rating. Related parameters: None. 124 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 125 Where X is 1, 2, or 3. Internal fault (PCB fault). The output from the current transformer circuit is not close enough to 0 when the SCRs are turned off. Troubleshooting • Contact the local Danfoss supplier for advice. • There are no related parameters to this trip message. 12.2.6 Depth Sensor Cause The smart card has detected a fault with the depth sensor.
  • Page 126 See also parameter 20-6 Motor Connection. 12.2.11 Flow Sensor Cause The smart card has detected a fault with the flow sensor. Troubleshooting • Check the following parameters: Parameter 30-5 Flow Sensor Type. Parameter 36-2 Flow Sensor. 126 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 127 ≤0.5 V AC. If the bypass contactor does not close, the voltage should be approximately 2 V AC. • Check that the cooling fans are operating (models MCD6-0042B~MCD6-0579B). 12.2.15 High Flow Cause The flow sensor connected to the smart card has activated high-flow protection. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 127...
  • Page 128 Parameter 7-3 Input A Trip Delay. Parameter 7-4 Input A Initial Delay. Parameter 7-5 Input B Function. Parameter 7-6 Input B Trip. Parameter 7-7 Input B Trip Delay. Parameter 7-8 Input B Initial Delay. 128 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 129 Where X is a number. This trip is not adjustable. The soft starter has tripped on an internal fault. Troubleshooting • Contact Danfoss with the fault code (X). 12.2.20 Internal Fault 88 Cause The soft starter firmware does not match the hardware.
  • Page 130 Parameter 30-7 Flow at 4 mA. Parameter 30-8 Flow at 20 mA. Parameter 31-2 Low Flow Trip Level. Parameter 31-3 Flow Start Delay. Parameter 31-4 Flow Response Delay. Parameter 36-7 Low Flow. 130 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 131 If the soft starter is connected to a grounded delta mains supply, adjust parameter 20-6 Motor Connection to match the motor connection configuration. • There are no parameters related to this trip message. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 131...
  • Page 132 Troubleshooting • Check the following parameter: Parameter 6-17 Motor Overtemperature. • Use the thermistor reset function to disable the thermistor circuit. • Check for a short circuit across terminals TER-05, TER-06. 132 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 133 The motor has experienced a sharp rise in power. Causes can include a momentary overload condition, which has exceeded the adjustable delay time. Troubleshooting • Check the following parameters: Parameter 5-13 Overpower. Parameter 5-14 Overpower Delay. Parameter 6-9 Overpower. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 133...
  • Page 134 Check the following parameters: Parameter 5-18 Phase Sequence. Parameter 6-16 Phase Sequence. 12.2.38 Power Loss Cause This trip is not adjustable. The soft starter is not receiving mains supply on 1 or more phases. 134 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 135 The smart card has detected a fault with the RTD sensor, or the RTD has activated temperature protection. Troubleshooting • Check the following parameters: Parameter 35-2 Temperature Trip Level. Parameter 36-10 RTD/PT100 B. 12.2.42 SCR Itsm Cause The SCR current surge rating has been exceeded. Related parameters: None. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 135...
  • Page 136 The resistance at the input has dropped below 20 Ω (the cold resistance of most thermistors is above this value) or • A short circuit has occurred. Related parameters: None. Troubleshooting • Check and resolve this condition. • There are no parameters related to this trip message. 136 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 137 Mains voltage has dropped below the level selected. Causes can include an undersized supply or adding a large load to the system. 12.2.51 Unsupported Option Cause The selected function is not available (for example jog is not supported in inside delta configuration). Related parameters: None. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 137...
  • Page 138: General Faults

    Troubleshooting 12.2.52 VZC Fail Px Cause Where X is 1, 2, or 3. Internal fault (PCB fault). Contact the local Danfoss supplier for advice. Related parameters: None. 12.2.53 Zero Speed Detect Cause The zero-speed detect input has not closed within the expected duration of a soft stop.
  • Page 139 [Back], the change is not saved. The soft starter does not show a confirmation. • Check that parameter 10-7 Adjustment Lock is set to Read & Write. If the parameter is set to Read Only, settings can be viewed but not changed. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 139...
  • Page 140 A USB function has been selected in the menu and the file has been found, but it does not contain the expected content. Rating not valid The value of parameter 20-4 Model Rating is incorrect. Parameter 20-4 Model Rating is not user-adjustable. Contact the local supplier for advice. 140 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 141: Appendix

    Parameter name. Parameter option. Parameter group name. • All dimensions in drawings are in metric values (imperial values in brackets). • An asterisk (*) indicates the default setting of a parameter. Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 141...
  • Page 142 Emergency mode Ethernet Excess start time 126, 139 LCP, local External control supply LCP, remote External zero-speed sensor LED descriptions Load settings Low battery Fault finding Low flow Features Low pressure 142 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 143 Protection settings 30, 41, 42, 140 Protocols Quick set-up Real-time clock Remote LCP Reset Reset command Reset input Reset thermistors Reverse operation Save settings SCR, failed Secondary motor settings Semiconductor fuses Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 143...
  • Page 144 Operating Guide | VLT® Soft Starter MCD 600 144 | Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174...
  • Page 145 Operating Guide | VLT® Soft Starter MCD 600 Danfoss A/S © 2018.10 AQ262141844215en-000202 / 175R1174 | 145...
  • Page 146 Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies.

Table of Contents