Table 156: 10-6 - Current Calibration
Range
Function
*100%
85–
Calibrates the soft starter's current monitoring circuits to match an external current metering device. Use the
115%
following formula to determine the necessary adjustment:
Calibration ( % )  =  
Table 157: 10-7 - Adjustment Lock
Option
*
Read & Write
Read Only
Table 158: 10-8 - User Parameter 1
Option
Blank
*
Current
Motor Voltage
P1 Voltage
P2 Voltage
P3 Voltage
Mains Frequency
Motor pf
Motor Power
Motor Temp (%)
Hours Run
Number of Starts
Pump Pressure
Pump Flow
Well Depth
Pump Temperature
Analog Output Value
104 | Danfoss A/S © 2018.10
Current shown on soft starter display
Current measured by external device
Function
Selects whether the LCP allows parameters to be changed via the Main Menu.
Allows altering of parameter values in the Main Menu.
Prevents users altering parameter values in the Main Menu.
Parameter values can still be viewed.
Function
Selects which information is shown on the main monitoring screen.
Shows no data in the selected area, allowing long messages to be shown without overlapping.
Average rms current across all 3 phases.
Average rms voltage across all 3 phases.
Phase 1 voltage.
Phase 2 voltage.
Phase 3 voltage.
The average frequency measured on 3 phases.
The motor's power factor, measured by the soft starter.
The motor's running power in kW.
The motor's temperature, calculated by the thermal model.
The number of hours the motor has run via the soft starter.
The number of starts the soft starter has completed since the start counter was last reset.
The pressure at the pump, as configured in parameters 30-2 to 30-4. This information is only available
if the smart card is installed.
The flow at the pump, as configured in parameters 30-6 to 30-11. This information is only available if
the smart card is installed.
The depth of the well, as configured in parameters 30-13 to 30-15. This information is only available if
the smart card is installed.
The pump temperature, as measured by the PT100. This information is only available if the smart card
is installed.
The value of the analog output (see parameter group 9-** Analog Output).
Programmable Parameters
AQ262141844215en-000202 / 175R1174