Parameter Group 33-** Pressure Control - Danfoss VLT MCD 600 Operating Manual

Hide thumbs Also See for VLT MCD 600:
Table of Contents

Advertisement

Operating Guide | VLT® Soft Starter MCD 600
Table 221: 32-5 - Low Pressure Start Delay
Range
* 0.5 s
00:00:100–
30:00:000
mm:ss:ms
Table 222: 32-6 - Low Pressure Response Delay
Range
* 0.5 s
00:00:100–30:00:000
mm:ss:ms

10.21 Parameter Group 33-** Pressure Control

The parameters in this group are only active if a smart card is installed.
Pressure control uses terminals B23, B24 on the smart card. Use an anlog 4–20 mA sensor.
Table 223: 33-1 - Pressure Control Mode
Option
Function
Selects how the soft starter uses data from the pressure sensor to control the motor.
*
Off
The soft starter does not use the pressure sensor to control soft starting.
Falling Pressure
The soft starter starts when the pressure drops below the level selected in parameter 33-2 Start Pressure
Start
Level.
Rising Pressure
The soft starter starts when the pressure rises above the level selected in parameter 33-2 Start Pressure Lev-
Start
el.
Table 224: 33-2 - Start Pressure Level
Range
Function
* 5
1–5000
Sets the pressure level to trigger the soft starter to perform a soft start.
Table 225: 33-3 - Start Response Delay
Range
* 0.5 s
00:00:100–30:00:000
mm:ss:ms
Table 226: 33-4 - Stop Pressure Level
Range
* 10
0–5000
Danfoss A/S © 2018.10
Function
Sets a delay before a low-pressure protection trip can occur. The delay is counted from the time a
start signal is received. The pressure is ignored until the start delay has elapsed.
Function
Sets a delay between the pressure passing the low-pressure trip level and the soft starter trip-
ping.
Function
Sets a delay between the pressure passing the pressure control start level and the soft starter per-
forming a soft start.
Function
Sets the pressure level to trigger the soft starter to stop the motor.
N O T I C E
Programmable Parameters
AQ262141844215en-000202 / 175R1174 | 115