12.2.31 Network Communication
Cause
The network master has sent a trip command to the soft starter, or there could be a network communication problem. Check the
network for causes of communication inactivity.
Troubleshooting
Check the following parameter:
-
Parameter 6-13 Network Communications.
12.2.32 Not Ready
Cause
The reset input may be active. If the reset input is active, the soft starter does not operate.
The soft starter may be waiting for the restart delay to elapse. The length of the restart delay is controlled by parameter 5-16 Restart
Delay.
Check the following parameters:
-
Parameter 5-16 Restart Delay.
-
Parameter 7-9 Reset/Enable Logic.
12.2.33 Overcurrent
Cause
The overcurrent has exceeded the level set in parameter 5-5 Overcurrent for longer than the time set in parameter 5-6 Overcurrent Delay.
Causes can include a momentary overload condition.
Troubleshooting
Check the following parameters:
-
Parameter 5-5 Overcurrent.
-
Parameter 5-6 Overcurrent Delay.
-
Parameter 6-5 Overcurrent.
12.2.34 Overpower
Cause
The motor has experienced a sharp rise in power. Causes can include a momentary overload condition, which has exceeded the
adjustable delay time.
Troubleshooting
Check the following parameters:
-
Parameter 5-13 Overpower.
-
Parameter 5-14 Overpower Delay.
-
Parameter 6-9 Overpower.
Danfoss A/S © 2018.10
Troubleshooting
AQ262141844215en-000202 / 175R1174 | 133