Environmental; Heat Dissipation; Motor Overload Protection; Certification - Danfoss VLT MCD 600 Operating Manual

Hide thumbs Also See for VLT MCD 600:
Table of Contents

Advertisement

Operating Guide | VLT® Soft Starter MCD 600

4.6 Environmental

Operating temperature
Storage temperature
Operating altitude
Humidity
Pollution degree
Vibration
Protection
MCD6-0020B~MCD6-0129B
MCD6-0144B~MCD6-0579B

4.7 Heat Dissipation

During start
During run
MCD6-0020B~MCD6-0042B
MCD6-0063B~MCD6-0129B
MCD6-0144B~MCD6-0244B
MCD6-0287B~MCD6-0579B

4.8 Motor Overload Protection

The default settings of parameters 1-4 to 1-6 provide motor overload
protection.

4.9 Certification

CE
UL/C-UL
Marine

4.10 Operational Life (Internal Bypass Contacts)

Expected operational lifetime
26 | Danfoss A/S © 2018.10
-10 to +60 °C (14–140 °F), above 40 °C (104 °F) with derating
0–1000 m (0–3280 ft), above 1000 m (3280 ft) with derating
Class 10, trip current 105% of FLA (full load amperage) or
Lloyds Marine No 1 specification
AQ262141844215en-000202 / 175R1174
Specifications
-25 to +60 °C (-13 to +140 °F)
5–95% relative humidity
Pollution degree 3
IEC 60068-2-6
IP20
IP00
4.5 W per ampere
≤ 35 W approximately
≤ 50 W approximately
≤ 120 W approximately
≤ 140 W approximately
equivalent
EN 60947-4-2
UL 508
ABS
DNV
100000 operations