9.8.2 Constant Current with Current Ramp

Current ramp soft starting raises the current from a specified starting level (1) to a maximum limit (3) over an extended period (2).
Current ramp starting can be useful for applications where:
The load can vary between starts (for example a conveyor which may start loaded or unloaded). Set parameter 2-3 Initial Current to
a level that will start the motor with a light load. Then, set parameter 2-4 Current Limit to a level that will start the motor with a
heavy load.
The load breaks away easily, but starting time has to be extended (for example a centrifugal pump where pipeline pressure has to
build up slowly).
The electricity supply is limited (for example a generator set), and a slower application of load allows greater time for the supply to
respond.