Danfoss VLT MCD 600 Operating Manual page 97

Hide thumbs Also See for VLT MCD 600:
Table of Contents

Advertisement

Operating Guide | VLT® Soft Starter MCD 600
Option
Motor Set Select
Reverse Direction
Pump Clean
Table 127: 7-2 - Input A Trip
Option
Always Active
*
Operating Only
Run Only
Table 128: 7-3 - Input A Trip Delay
Range
*0 s
0:00–4:00 (minutes:seconds)
Table 129: 7-4 - Input A Initial Delay
Range
* 0 s
00:00–30:00 (minutes:seconds)
Table 130: 7-5 - Input B Function
Option
*
Input Trip (N/O)
Input Trip (N/C)
Emergency Mode
Jog Forward
Jog Reverse
Zero Speed Sensor
Motor Set Select
Reverse Direction
Pump Clean
Danfoss A/S © 2018.10
Function
A closed circuit across DI-A, COM+ instructs the soft starter to use the secondary motor configuration
for the next start/stop cycle.
A closed circuit across DI-A, COM+ instructs the soft starter to reverse the phase sequence for the
next start.
Activates the pump clean function.
Function
Selects when an input trip can occur.
A trip can occur at any time when the soft starter is receiving power.
A trip can occur while the soft starter is running, stopping, or starting.
A trip can only occur while the soft starter is running.
Function
Sets a delay between the input activating and the soft starter tripping.
Function
Sets a delay before an input trip can occur.
The initial delay is counted from the time a start signal is received.
The state of the input is ignored until the initial delay has elapsed.
Function
Selects the function of Input B. See parameter 7-1 Input A Function for details.
Programmable Parameters
AQ262141844215en-000202 / 175R1174 | 97