Operating Guide | VLT® Soft Starter MCD 600
Table 146: 8-10 - Main Contactor Time
Range
Function
*400 ms
100–2000
Sets the delay period between the soft starter switching the main contactor output (terminals 13, 14) and
ms
beginning the pre-start checks (before a start), or entering the not-ready state (after a stop). Set according
to the specifications of the main contactor used.
10.13 Parameter Group 9-** Analog Output
Table 147: 9-1 - Analog Output A
Option
*
Current (% FLC)
Motor Temp (%)
Motor pf
Motor Power (%kW)
Heat Sink Temperature (°C)
Table 148: 9-2 - Analog A Scale
Range
0–20 mA
*
4–20 mA
Table 149: 9-3 - Analog A Maximum Adjustment
Range
Function
* 100%
0–600%
Calibrates the upper limit of the analog output to match the signal measured on an external current measur-
ing device.
Table 150: 9-4 - Analog A Minimum Adjustment
Range
Function
* 0%
0–600%
Calibrates the lower limit of the analog output to match the signal measured on an external current measuring
device.
10.14 Parameter Group 10-** Display
Table 151: 10-1 - Language
Option
102 | Danfoss A/S © 2018.10
Function
Selects the information reported via the analog output.
Current as a percentage of motor full load current.
The motor's temperature, calculated by the thermal model.
Motor power factor, measured by the soft starter.
Motor power, as a percentage of the programmed power.
The soft starter's temperature, measured at the heat sink.
Function
Selects the range of the analog output.
Function
Selects in which language the LCP shows messages and feedback.
Programmable Parameters