Operating Guide | VLT® Soft Starter MCD 600
12.2.4 Current Imbalance
Cause
An imbalance in the incoming mains voltage.
A problem with the motor windings.
A light load on the motor.
A phase loss on mains terminals L1, L2, or L3 during Run mode.
An SCR that has failed open circuit. A failed SCR can only be diagnosed accurately by replacing the SCR and checking the soft
starter performance.
Troubleshooting
Check the following parameters:
-
Parameter 5-1 Current Imbalance.
-
Parameter 5-2 Current Imbalance Delay.
-
Parameter 6-3 Current Imbalance.
12.2.5 Current Read Err Lx
Cause
Where X is 1, 2, or 3. Internal fault (PCB fault). The output from the current transformer circuit is not close enough to 0 when the SCRs
are turned off.
Troubleshooting
Contact the local Danfoss supplier for advice.
There are no related parameters to this trip message.
12.2.6 Depth Sensor
Cause
The smart card has detected a fault with the depth sensor.
Troubleshooting
Check the following parameters:
-
Parameter 30-12 Depth Sensor Type.
-
Parameter 36-3 Depth Sensor.
12.2.7 EEPROM Fail
Cause
An error occurred loading data from the EEPROM to RAM when the LCP powered up.
Troubleshooting
If the problem persists, contact the local distributor.
There are no parameters related to this trip message.