Operating Guide | VLT® Soft Starter MCD 600
Table 202: 30-5 - Flow Sensor Type
Option
*
None
Switch
Analog
Pulses per minute
Pulses per unit
Table 203: 30-6 - Flow Units
Option
*
liters/second
liters/minute
gallons/second
gallons/minute
Table 204: 30-7 - Flow at 4 mA
Range
Function
*0
0–5000
Calibrates the soft starter to the 4 mA (0%) level of the flow sensor input.
Table 205: 30-8 - Flow at 20 mA
Range
Function
*0
0–5000
Calibrates the soft starter to the 20 mA (100%) level of the flow sensor input.
Table 206: 30-9 - Units per Minute at Max Flow
Range
Function
*0
0–5000
Calibrates the soft starter to the maximum flow volume of the flow sensor.
Table 207: 30-10 - Pulses per Minute at Max Flow
Range
Function
*0
0–20000
Calibrates the soft starter to the maximum flow volume of the flow sensor.
Table 208: 30-11 - Units per Pulse
Range
Function
*0
0–1000
Set to match how many units the flow sensor measures for each pulse.
112 | Danfoss A/S © 2018.10
Function
Selects which type of sensor is associated with the flow sensor input on the smart card.
Function
Selects which units the sensor uses to report the measured flow.
Programmable Parameters
AQ262141844215en-000202 / 175R1174