Parameter Group 700, All Parameters; Parameter Group 700 Definitions - Danfoss Cascade Operating Instructions Manual

Controller option
Table of Contents

Advertisement

Parameter group 700 definitions

Para
Name
Description
712
PUMP COMBINA-
Selects number and size of
TION
slave pumps
713
STAGING BANDW.
Pump Staging Bandwidth in
%
% of setpoint
714
DESTAGING DELAY
Pump Staging Bandwidth off
715
STAGING DELAY
Pump Staging Bandwidth on
716
OVERRIDE
Over-ride Bandwidth
BANDW.%
717
OVERRIDE TIMER
Over-ride Bandwidth
hysteresis time
718
STAGING FREQ%
VLT Frequency at staging
transition in % of max speed
721
DESTAGE TIME
Destage timer
722
PUMP CYCLING
Enable or disable pump
cycling
723
OPERATIONAL
Selects either Standard or
MODE SELECT
Master/Slave control
724
PUMP 2 ON TIME
Hour meter for pump 2
725
PUMP 3 ON TIME
Hour meter for pump 3
726
PUMP 4 ON TIME
Hour meter for pump 4
727
PUMP 5 ON TIME
Hour meter for pump 5
728
PUMP 2 CYCLES
Cycle counter for pump 2
729
PUMP 3 CYCLES
Cycle counter for pump 3
730
PUMP 4 CYCLES
Cycle counter for pump 4
731
PUMP 5 CYCLES
Cycle counter for pump 5
736
RELAY ON TIME
Relay hour meter, relay R6 -
R9
737
RELAY CYCLES
Relay Cycle counter, rela
738
SETPOINTS HM 1- 7
Calculated intermediate
setpoint, relay (Hm1-Hm7)
739
M/S STAGE FREQ
M/S Stage on frequency, relay
(1-4)
740
M/S DESTAGE FREQ
M/S Stage off frequency, relay
(1-4)
Conversion Index Factors
Conversion Index
74
2
1
0
-1
-2
-3
-4
MG.60.I3.02 - VLT is a registered Danfoss trademark
Unit
No.
%
Sec.
Sec.
%
Sec.
%
Sec.
Hrs
Hrs
Hrs
Hrs
No.
No.
No.
No.
Hrs
No.
Para
415
Hz
Hz
Conversion Factor
3.6
100.0
10.0
1.0
0.1
0.01
0.001
0.0001
Cascade Controller Option
Range
Factory
Setting
1 - 8
R6@100
1.0 - 100.0
5.0%
0.0 - 3000.0
10 sec.
0.0 - 3000.0
10 sec.
2.0 - 100.0
100%
0.0 - 300
10 sec.
0.0 - 100.0
90%
Para 403 - 600
OFF
Enabled/Disabled
Enable
Standard/Master
Standard
Slave
0 - 130000
0.0
0 - 130000
0.0
0 - 130000
0.0
0 - 130000
0.0
0 - 130000
0.0
0 - 130000
0.0
0 - 130000
0.0
0 - 130000
0.0
0 - 130000
0.0
0 - 130000
0.0
H0 - H1
0.000
Para 201-202
Para 202
Para 201-202
Para 201
DataType Descriptions
Data type
3
4
5
6
7
9
Change
Data Type
Conversion
During
Index
Operation
No
5
0
Yes
6
-1
Yes
6
-1
Yes
6
-1
Yes
6
-1
Yes
6
-1
Yes
6
-1
Yes
6
0
No
5
0
No
5
0
Yes
7
-1
Yes
7
-1
Yes
7
-1
Yes
7
-1
Yes
7
0
Yes
7
0
Yes
7
0
Yes
7
0
No
7
-1
No
7
-1
No
4
-3
Yes
6
-1
Yes
6
-1
Description
Integer 16
Integer 32
Unsigned 8
Unsigned 16
Unsigned 32
Text string