12.2.35 Overvoltage
Cause
There has been a voltage surge on the mains. Causes can include problems with a transformer tap regulator of off-loading of a large
transformer load.
Troubleshooting
Check the following parameters:
-
Parameter 5-9 Overvoltage.
-
Parameter 5-10 Overvoltage Delay.
-
Parameter 6-7 Overvoltage.
12.2.36 Parameter Out of Range
Cause
This trip is not adjustable.
A parameter value is outside the valid range. The LCP indicates the first invalid parameter.
An error occurred loading data from the EEPROM to RAM when the LCP powered up.
The parameter set or values in the LCP do not match the parameters in the soft starter.
Load User Set has been selected but no saved file is available.
Troubleshooting
Reset the fault. The soft starter loads the default settings.
If the problem persists, contact the local distributor.
There are no parameters related to this trip message.
12.2.37 Phase Sequence
Cause
The phase sequence on the soft starter mains terminals (L1, L2, L3) is not valid.
Troubleshooting
Check the phase sequence on L1, L2, and L3, and ensure that the setting in parameter 5-18 Phase Sequence is suitable for the
installation.
Check the following parameters:
-
Parameter 5-18 Phase Sequence.
-
Parameter 6-16 Phase Sequence.
12.2.38 Power Loss
Cause
This trip is not adjustable. The soft starter is not receiving mains supply on 1 or more phases.