Operating Guide | VLT® Soft Starter MCD 600
Table 32: 2-6 - Kickstart Time
Range
*0000 ms
0–2000 ms
Table 33: 2G - Kickstart Level
Range
Function
* 500%
100–700%
Sets the level of the kickstart current.
FLC
Table 34: 2-8 - Jog Torque
Range
Function
* 50%
20–100%
The VLT® Soft Starter MCD 600 can jog the motor at a reduced speed, which allows precise positioning of belts
and flywheels. Jog can be used for either forward or reverse operation.
Set the current limit for jog operation.
Table 35: 2-9 - Stop Mode
Option
Coast To Stop
*
TVR Soft Stop
Adaptive Control
DC Brake
Soft Brake
Table 36: 2-10 - Stop Time
Range
* 0 s
0:00–4:00 (mi-
nutes:seconds)
Table 37: 2-11 - Adaptive Stop Profile
Option
Early Deceleration
*
Constant Deceleration
80 | Danfoss A/S © 2018.10
Function
Sets the kickstart duration. A setting of 0 disables kickstart.
Kickstart subjects the mechanical equipment to increased torque levels. Ensure that the motor,
load, and couplings can handle the additional torque before using this feature.
Function
Sets the time for soft stopping the motor using TVR or adaptive control. If a main contactor is installed,
the contactor must remain closed until the end of the stop time. Use the main contactor output (13,
14) to control the main contactor.
Function
Selects which profile the VLT® Soft Starter MCD 600 uses for an adaptive control soft stop.
N O T I C E
Function
Selects the stop mode.
Programmable Parameters
AQ262141844215en-000202 / 175R1174