Operating Guide | VLT® Soft Starter MCD 600
13, 14 Main contactor output
Not using fuses or circuit breakers voids the guarantee.
Illustration 11:
Wiring of an Inside Delta Installation

5.8 Typical Installation

The VLT® Soft Starter MCD 600 is installed with a main contactor (AC3-rated). Control voltage must be supplied from the input side of
the contactor.
The main contactor is controlled by the main contactor output (13, 14).
1
K1
F1
1/L1
3/L2
5/L3
A7
A8
A9
RESET
S1
COM+
START
S2
COM+
DI-A
DI-B
TER-05
TER-06
1 Three-phase supply
3 Control voltage (soft starter)