Operating Guide | VLT® Soft Starter MCD 600
5 Motor thermistor input
7 Analog output
9 Pilot lamps
K1 Main contactor
RESET, COM+ (S1) Reset
DI-A, COM+ Programmable input A (default = Input trip (N/O))
TER-05, TER-06 Motor thermistor input
21, 22, 23 Relay output A (default = Run)
AO-07, AO-08 Analog output
Illustration 12:
Installation Example

5.9 Quick Set-up

The Quick Set-up makes it easy to configure the soft starter for common applications. The VLT® Soft Starter MCD 600 guides through
the most common installation parameters and suggests a typical setting for the application. Adjust each parameter to suit the exact
requirements.
All other parameters remain at default values. To change other parameter values or review default settings, use the Main Menu (see
10.4 Parameter List
for details).
Always set parameter 1-2 Motor Full Load Current to match the motor nameplate FLC.
Table 16: Suggested Settings for Common Applications
Application
Start mode
Pump centrifu-
Adaptive con-
gal
trol
Pump bore
Adaptive con-
trol
Pump hydraul-
Constant cur-
ic
rent
Fan damped
Constant cur-
rent
Fan undamped
Constant cur-
rent
Compressor
Constant cur-
screw
rent
Compressor re-
Constant cur-
cip
rent
Conveyor
Constant cur-
rent
Danfoss A/S © 2018.10
Start
Initial
Cur-
ramp
current
rent
time [s]
[%]
limit
[%]
10
200
500
3
200
500
2
200
350
2
200
350
2
200
450
2
200
400
2
200
450
5
200
450
6 Relay outputs
8 Control voltage (external equipment)
10 Communications/smart card expansion port
F1 Semiconductor fuses
START, COM+ (S2) Start/stop
DI-B, COM+ Programmable input B (default = Input trip (N/O))
13, 14 Main contactor output
33, 34 Relay output B (default = Run)
Adaptive
Stop mode
start profile
Early acceler-
Adaptive
ation
control
Early acceler-
Adaptive
ation
control
n/a
Coast to stop
n/a
Coast to stop
n/a
Coast to stop
n/a
Coast to stop
n/a
Coast to stop
n/a
Coast to stop
AQ262141844215en-000202 / 175R1174 | 37
Installation
Stop
Adaptive
time [s]
stop profile
15
Late deceler-
ation
3
Late deceler-
ation
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a