Operating Guide | VLT® Soft Starter MCD 600
Parameter group number
5-8
5-9
5-10
5-11
5-12
5-13
5-14
5-15
5-16
5-17
5-18
6
6-1
6-2
6-3
6-4
6-5
6-6
6-7
6-8
6-9
6-10
6-11
6-12
6-13
6-14
6-15
6-16
6-17
6-18
6-19
6-20
7
7-1
7-2
Danfoss A/S © 2018.10
Parameter group name
Undervoltage Delay
Overvoltage
Overvoltage Delay
Underpower
Underpower Delay
Overpower
Overpower Delay
Excess Start Time
Restart Delay
Starts per Hour
Phase Sequence
Protection Actions
Auto-Reset Count
Auto-Reset Delay
Current Imbalance
Undercurrent
Overcurrent
Undervoltage
Overvoltage
Underpower
Overpower
Excess Start Time
Input A Trip
Input B Trip
Network Communications
Remote Keypad Fault
Frequency
Phase Sequence
Motor Overtemperature
Motor Thermistor Circuit
Shorted SCR Action
Battery/Clock
Inputs
Input A Function
Input A Trip
Programmable Parameters
Default setting
00:01 (mm:ss)
500 V
00:01 (mm:ss)
10%
00:01 (mm:ss)
150%
00:01 (mm:ss)
00:20 (mm:ss)
00:10 (mm:ss)
0
Any Sequence
0
00:05 (mm:ss)
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
Log Only
Log Only
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
Soft Trp and Log
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
3-Phase Control Only
Soft Trip and Log
Input Trip (N/O)
Operating Only
AQ262141844215en-000202 / 175R1174 | 73