Operating Guide | VLT® Soft Starter MCD 600
Troubleshooting
For the soft starter and the motor, check
-
The supply connections.
-
The input connections.
-
The output connections.
There are no parameters related to this trip message.
12.2.23 L1-T1/L2-T2/L3-T3 Shorted
Cause
During pre-start checks, the soft starter has detected a short-circuited SCR or a short circuit within the bypass contactor as indicated.
Troubleshooting
Consider using PowerThrough to allow operation until the soft starter can be repaired.
See also parameter 6-19 Shorted SCR Action.
12.2.24 Low Control Volts
Cause
The soft starter has detected a drop in the internal control voltage. This protection is not active in ready state.
Troubleshooting
Check the external control supply (terminals A7, A8, A9) and reset the soft starter.
If the external control supply is stable:
-
Check if the 24 V supply on the main control PCB is faulty; or
-
Check if the bypass driver PCB is faulty. Contact the local supplier for advice.
There are no parameters related to this trip message.
12.2.25 Low Flow
Cause
The flow sensor connected to the smart card has activated low-flow protection. Related parameters:
Troubleshooting
Check the following parameters:
Parameter 30-5 Flow Sensor Type.
-
-
Parameter 30-7 Flow at 4 mA.
-
Parameter 30-8 Flow at 20 mA.
-
Parameter 31-2 Low Flow Trip Level.
-
Parameter 31-3 Flow Start Delay.
-
Parameter 31-4 Flow Response Delay.
-
Parameter 36-7 Low Flow.