Configuration Of Inputs And Outputs - Danfoss AK-PC 781A User Manual

Capacity controller with recovery function
Table of Contents

Advertisement

Configuration - continued
Configuration of inputs
and outputs
1. Go to Configuration menu
2. Select I/O configuration
3. Configuration of Digital outputs
Press the +-button to go on to the
next page
4. Setup On/off inputs
74
The following displays will depend on the earlier definitions. The dis-
plays will show which connections the earlier settings will require. The
tables are the same as shown earlier.
• Digital outputs
• Digital inputs
• Analog outputs
• Analog inputs
Load
Solenoid valve, oil, Comp. 1
Solenoid valve, oil, Comp. 2
Solenoid valve, oil, Comp. 3
Solenoid valve, oil, Comp. 4
Solenoid valve, oil separator
Circulation pump tw
Circulation pump hr
Room fan
Compressor 1
Compressor 2
Compressor 3
Compressor 4
Start /stop of VLT for fans
3-way valve, tap water, V3tw
3-way valve, Heat circuit, V3hr
3-way valve, gas cooler, V3gc
We set up the controller's digital outputs by keying in which module
and point on this module each one of these has been connected to.
We furthermore select for each output whether the load is to be active
when the output is in pos. ON or OFF.
Attention! Relay outputs must not be inverted at unloader valves. The
controller inverts the function itself.
There will be no voltage at the bypass valves when the compressor is not
in operation. Power is connected immediately before the compressor is
started.
Function
External compressor stop
Level switch, oil, comp.1
Level switch, oil, comp.2
Level switch, oil, comp.3
Level switch, oil, comp.4
Level switch, oil, receiver High
Level switch, oil, receiver Low
Level switch, oil, Separator
Level switch, CO2 receiver
Reset of compressor stop
Compressor 1 Gen. Safety
Compressor 2 Gen. Safety
Compressor 3 Gen. Safety
Compressor 4 Gen. Safety
Start/stop of heat recovery hr
All compressors common safety
Flow switch FStw
Flow switch FShr
Start/stop of heat recovery tw
We set up the controller's digital input functions by keying in which
module and point on this module each one of these has been connected
to.
We furthermore select for each output whether the function is to be ac-
tive when the output is in pos. Closed or Open.
Open has been selected here for all the safety circuits. This means that
the controller will receive signal under normal operation and register it
as a fault if the signal is interrupted.
Capacity controller RS8HE202 © Danfoss 2017-07
Output
Module
Point
Active at
DO1
1
12
DO2
1
13
DO3
1
14
DO4
1
15
DO5
1
16
D06
1
17
DO7
1
18
DO8
1
19
DO1
2
9
DO2
2
10
DO3
2
11
DO4
2
12
DO5
2
13
DO6
2
14
DO7
2
15
DO8
2
16
Input
Module
Point
Active at
AI4
1
4
Closed
AI8
1
8
Closed
AI9
1
9
Closed
AI10
1
10
Closed
AI11
1
11
Closed
AI1
2
1
Closed
AI2
2
2
Closed
AI3
2
3
Closed
AI4
2
4
Open
AI5
2
5
Pulse signal
DI1
4
1
Open
DI2
4
2
Open
DI3
4
3
Open
DI4
4
4
Open
DI5
4
5
Closed
DI6
4
6
Open
DI7
4
7
Open
DI8
4
8
Open
AI2
5
3
Closed
3 - Outputs
The possible functions are
the following:
Comp. 1
Unloader 1-1
Unloader 1-2
Unloader 1-3
Do for Compressor. 2-8
ON
Oil valve comp. 1-8
ON
Lp comp. oil pulse
ON
Oil valve 1-4 (8)
Oil valve separat. 1-8
ON
MT Comp. release
ON
LT Comp. request
ON
Injection heat exchanger
ON
Injection suction line
ON
Injection ON
ON
Fan 1
ON
Fan 2 - 8
HP Control
ON
Valve gas cooler V3gc
ON
Heat recovery
ON
Valve tap water V3tw
ON
Pump tap water tw
ON
Valve heat recov. V3hr
ON
Pump heat recov. hr
Additional heat
Alarm
I'm alive relay
Thermostat 1 - 5
Pressostat 1 - 5
Volt input 1 - 5
PI 1-3
4 - Digital inputs
The possible functions are
the following:
Ext. Main switch
Ext. compr. stop
Ext. power loss
Night setback
Load shed 1
Load shed 2
LT Comp. Release
MT Comp. Request
All compressors:
Common safety
Comp. 1
Oil pressure safety
Over current safety
Motor protect. safety
Disch. temp. safety
Disch. press. safety
General safety
VSD comp. Fault
Do for Comp. 2-8
Fan 1 safety
Do for fan 2-8
VSD cond safety
Reset comp. lockout
LP comp.oil counter
Oil receiver low
Oil receiver high
Oil level comp.1-8
Oil separator low 1-8
Oil separator high 1-8
Heat recovery
tw enable
hr enable
Flow switch tw
Flow switch hr
DI 1 Alarm input
DI 2-10 ...
PI-1 Di ref
External DI PI-1
AK-PC 781A