Superheat controller, Type EKE 1A, 1B, 1C, 1D
Table 14: ETS 5M
Wire color
EKE terminals
Figure 9: ETS/KVS colibri
ETS / KVS
Colibri® and
CCMT valves
white
black
red
green
Guideline for long M12 cables on Danfoss stepper motor valves
• Long cables will lead to degradation of performance
• You can overcome this degradation by changing the settings for the valve driver. This guideline is based on the
cable type being the same type as the standard Danfoss stepper motor cable
Table 15: Recommended wire size and cable distance (twisted pair) between EKE controller and stepper motor valve
Cable length
Wire diameter
Tip for updating I028 parameter for 15m-30m cables:
1.
Use koolProg online service option (EKE should be connected)
2.
Select the desired valve first
3.
Again chnage to user defined option, the valve default settings of previous selcted valve will be loaded
automatically
4.
Change only the I028 parameter. According to the value in below table
Table 16: Parameter setting for long M12 cable 15 - 30 m
Product
ETS 12C - ETS 100C
KVS 2C - KVS 5C
ETS 12.5 - ETS 400
KVS 15 - KVS 42
CTR 20
CCMT 2 - CCMT 8
CCM 10 - CCM 40
ETS 6
CCMT 0
CCMT 1
CCMT 16 - CCMT 42
ETS 5M

3.5 Connecting Relay Outputs

EKE1 series has 1 relay output
• Type SPDT relay. Digital Output can be used to connect either a solenoid valve or an alarm
© Danfoss | Climate Solutions | 2022.06
Brown
Black
A1
A2
ETS6 valve
ETS5M valves
orange
Brown
yellow
black
orange
red
black
yellow
0.52 / 0.33 mm
Orange
B1
A1
A1
A2
A2
B1
B1
B2
B2
1 m – 15 m
2
20 / 22 AWG
I028 Valve drive current
925mA peak
200 mA peak
270mA peak
270mA peak
400mA peak
450mA peak
190mA peak
Yellow
Red
B2
Not connected
15 m – 30 m
Min. 0.52 mm
2
20 AWG
BC398828796060en-000101 | 14