Execution method of data restoration
The target device for data restoration can be set with a program.
■Acquiring a right to use
Set a value within the range from 1000H to 1FFFH to SD1435.
Right to use for data backup
• Special relays (SM) and special registers (SD) are used for data restoration.
• To prevent the same special relay (SM) and special register (SD) from being set at the same time, acquiring
a right to use of them for data backup is required.
• To acquire a right to use, specify a value which is not duplicate with values for other request sources to
SD1435, and check that the value set to SD1435 is stored to SD1436.
• Normal operation cannot be assured if the data backup function is performed without confirming the
acquisition of a right to use.
■Setting the restoration setting
1.
Setting a target module type
Set the target module type for data restoration to the lower 8 bits of SD1437.
Target module type
2H: CC-Link
2.
Setting an execution unit
Set the unit of execution for data restoration to the upper 8 bits of SD1437.
Execution unit
1H: Module unit
2H: Station unit
3H: Station sub-ID unit
3.
Selecting a folder for data restoration
Set the number for backup folder name, from which data is to be restored, to SD1438.
Target folder
00 to 99: Target folder specification
4 CC-Link
88
4.5 Backing up/Restoring Data of Devices Supporting iQSS
Description
Set the target module type.
Description
Set this to specify all devices supporting iQSS which are connected to the CC-Link master/local module with the
specified start I/O number.
Set this to specify either of the following devices supporting iQSS which are connected to the CC-Link master/local
module with the specified start I/O number: device supporting iQSS with the specified station number or all devices
supporting iQSS which are connected to the module with the specified station number.
Set this to specify the device supporting iQSS with the specified station sub-ID number which is connected to the
module with the specified station number among the devices supporting iQSS which are connected to the CC-Link IE
Field Network master/local module with the specified start I/O number.
Description
Specify the number among the numbers for backup folder name, 00 to 99.