Execution method of data backup
The target device for data backup can be set with a program.
■Acquiring a right to use
Set a value within the range from 1000H to 1FFFH to SD1435.
Right to use for data backup
• Special relays (SM) and special registers (SD) are used for data backup.
• To prevent the same special relay (SM) and special register (SD) from being set at the same time, acquiring
a right to use of them for data backup is required.
• To acquire a right to use, specify a value which is not duplicate with values for other request sources to
SD1435, and check that the value set to SD1435 is stored to SD1436.
• Normal operation cannot be assured if the data backup function is performed without confirmation of the
right-to-use acquisition.
■Setting the backup setting
1.
Setting a target module type
Set the target module type for data backup to the lower 8 bits of SD1437.
Target module type
4H: CC-Link IE Field Network
2.
Setting an execution unit
Set the unit of execution for data backup to the upper 8 bits of SD1437.
Execution unit
1H: Module unit
2H: Station unit
3H: Station sub-ID unit
3.
Setting a number for a data backup folder name
Set the number for a backup folder name to SD1438.
Target folder
FFFFH: Automatic specification
(default)
FFFEH: Automatic specification
(folder deletion supported)
00 to 99: Target folder specification
Description
Set the target module type.
Description
Set this to specify all devices supporting iQSS which are connected to the CC-Link IE Field Network master/local
module with the specified start I/O number.
Set this to specify either of the devices supporting iQSS which are connected to the CC-Link IE Field Network master/
local module with the specified start I/O number: device supporting iQSS with the specified station number or all
devices supporting iQSS which are connected to the module with the specified station number.
Set this to specify the device supporting iQSS with the specified station sub-ID number which is connected to the
module with the specified station number among the devices supporting iQSS which are connected to the CC-Link IE
Field Network master/local module with the specified start I/O number.
Description
Use the smallest number for a new backup folder name among the unused numbers as the backup folder name.
An error occurs when unused number is no longer available due to such cases as the number of folders reached the
upper limit.
Use the smallest number for a new backup folder name among the unused numbers as the backup folder name.
The oldest folder is deleted and the number of the deleted folder is used for a new backup folder name when unused
number is no longer available due to such cases as the number of folders reached the upper limit.
Set the number for a backup folder name.
When another folder with the same number exists, the operation will be as follows:
■For module unit
• The backup folder with the same number is deleted, and a new backup folder is created.
■For station unit or station sub-ID unit
• Data in the backup folder with the same number is overwritten.
5.5 Backing up/Restoring Data of Devices Supporting iQSS
5 CC-Link IE Field Network
5
115