■Setting the backup setting
1.
Setting a target module type
Set a target module with the lower 8 bits of SD1362 (iQ Sensor Solution data backup/restoration target module, execution unit
setting).
Target module type
1H: AnyWireASLINK
2.
Setting an execution unit
Set a unit to specify the range of data to be backed up at once.
Specify the execution unit to the upper 8 bits of SD1362.
Execution unit
1H: Module unit
2H: ID unit
3.
Setting a number for a data backup folder name
Set a folder number to SD1363 (iQ Sensor Solution backup/restoration folder number setting).
Target folder
FFFFH: Automatic specification (default)
FFFEH: Automatic specification (folder
deletion supported)
0 to 99: Target folder specification
*1 When the specified folder number exists, the operation to be performed depends on the specification of the execution unit as follows:
Execution unit
1H: Module unit
2H: ID unit
4.
Setting a target device
• Setting a module
When '1H' (module unit) is set for the execution unit, set a start I/O number to SD1364 (iQ Sensor Solution data backup/
restoration target setting (target module)).
In a multiple CPU system, only the AnyWireASLINK master module controlled by a host CPU can be backed up. Data backup
cannot be performed for non-controlled modules.
Target device (Module)
0 to FFH: Start I/O number
• Setting an ID number
When '2H' (ID unit) is set for the execution unit, set an ID number to SD1365 (iQ Sensor Solution data backup/restoration
target setting (target device 1)).
Target device (ID number)
0 to 9999: ID number
Description
Set this to specify a device supporting iQSS which is connected to the AnyWireASLINK master module.
Description
Set this to specify all devices supporting iQSS which are connected to the AnyWireASLINK master module with
the specified start I/O number.
Set this to specify the device supporting iQSS with the specified ID number among the devices which are
connected to the AnyWireASLINK master module with the specified start I/O number.
Description
Among the numbers (0 to 99) that are not used for backup folder names, the smallest number is used for a new
backup folder name.
An error occurs when unused number is no longer available due to such cases as the number of folders reached
the upper limit.
Among the numbers (0 to 99) that are not used for backup folder names, the smallest number is used for a new
backup folder name.
The oldest backup folder (date_number) is deleted and the number of the deleted folder is used for a new backup
folder name when unused number is no longer available due to such cases as the number of folders reached the
upper limit.
Specify a number (0 to 99) of the backup folder name.
When another folder with the same number exists, the target data is overwritten in execution unit without
*1
changing the folder name.
Operation
When the backup data with the same target module exists, the backup folder (start I/O number_ID) is deleted
before performing data backup.
When the backup data with the same target module and the same target ID exists, the backup folder (start I/O
number_ID) is deleted before performing data backup.
Description
Set the start I/O number (the value obtained by dividing the start I/O number by 16) of the AnyWireASLINK
master module which is connected to a target device supporting iQSS.
Description
Set the ID number of a target device supporting iQSS.
7.4 Backing up/Restoring Data of Devices Supporting iQSS
7 AnyWireASLINK
177
7