■Communication load
When data is backed up or restored, the load of the service processing in the CPU module is temporarily increased.
Consequently, a communication response will be slow and a timeout error may occur in other communications.
To avoid a timeout error, review the value set for "Device/Label Access Service Processing Setting".
[CPU Parameter] [Service Processing Setting] [Device/Label Access Service Processing Setting]
■Data backup/restoration for CC-Link IE Field Network master station
• Data backup in station sub-ID unit: When a folder storing backup data of a station (the I/O numbers and station numbers
are the same) is specified and the data is backed up again, use a module of the same model as that of the CC-Link IE Field
Network master station which has been used for data backup.
• Data restoration: Use a module of the same model as that of the CC-Link IE Field Network master station which has been
used for data backup.
■Multiple CC-Link IE Field Network master stations are mounted on a single base unit
Do not perform data backup/restoration when multiple CC-Link IE Field Network master stations having an identical network
number are mounted on a base unit. Data cannot be backed up/restored properly.
■Change of backup folders/data
Do not change a backup folder name, configuration, or saved file.
Otherwise, the data may not be restored properly.
For the backup file capacity, refer to the following section.
Page 368 Backup File Capacity
9.4 Backing up/Restoring Data of Devices Supporting iQSS