5.
Setting the operation setting when a data restoration error occurs
Set the operation on error to the lower 8 bits of SD1444 in order to in order to restore data for multiple devices supporting
iQSS.
Operation on error
0H: Continue
1H: Stop
■Performing a data restoration
Data is restored if SM1439 is turned ON while SD1446 is '1H' (ready).
Once data is restored, SD1446 will be '2H' (being executed).
■Requiring a data restoration cancellation
The data restoration stops if SM1442 is turned ON while SD1446 is '1H' (ready) or '2H' (being executed).
■Releasing the right to use
When SM1435 is turned ON after a data restoration is completed (including a cancellation or an error), the right to use is
released and the next data restoration is ready to be performed.
SM1435 turns ON to OFF when the right to use is released.
If the right to use is released even though it has already been done, SM1435 remains ON since no processing is performed.
In that case, set SM1435 to OFF.
3 AnyWireASLINK
48
3.5 Backing up/Restoring Data of Devices Supporting iQSS
Description
Set this to continue a data restoration even if it fails on some devices while being performed to multiple devices
supporting iQSS.
Set this to stop a data restoration even if it fails on some devices while being performed to multiple devices supporting
iQSS.