■Setting the backup setting
1.
Setting a target module type
Set a target module with the lower 8 bits of SD1362 (iQ Sensor Solution data backup/restoration target module, execution unit
setting).
Target module type
4H: CC-Link IE Field Network
2.
Setting an execution unit
Set a unit to specify the range of data to be backed up at once.
Specify the execution unit to the upper 8 bits of SD1362.
Execution unit
1H: Module unit
2H: Station unit
3H: Station sub-ID unit
3.
Setting a number for a data backup folder name
Set a folder number to SD1363 (iQ Sensor Solution backup/restoration folder number setting).
Target folder
FFFFH: Automatic specification (default)
FFFEH: Automatic specification (folder
deletion supported)
0 to 99: Target folder specification
*1 When the specified folder number exists, the operation to be performed depends on the specification of the execution unit as follows:
Execution unit
1H: Module unit
2H: Station unit
3H: Station sub-ID unit
9 CC-Link IE Field Network
260
9.4 Backing up/Restoring Data of Devices Supporting iQSS
Description
Set this to specify a device supporting iQSS which is connected to the CC-Link IE Field Network master station.
Description
Set this to specify the device supporting iQSS which is connected to the own network among the devices which
are connected to a CC-Link IE Field Network master station with the specified start I/O number.
Set this to specify either of the following iQSS supported devices which are connected to a CC-Link IE Field
Network master station with the specified start I/O number: the devices supporting iQSS with the specified
station number or all devices supporting iQSS which are connected to the specified station number.
Set this to specify the following devices supporting iQSS which are connected to a CC-Link IE Field Network
master station with the specified start I/O number: the devices which are connected to the specified station
number with the specified station sub-ID number.
Description
Among the numbers (0 to 99) that are not used for backup folder names, the smallest number is used for a new
backup folder name.
An error occurs when unused number is no longer available due to such cases as the number of folders reached
the upper limit.
Among the numbers (0 to 99) that are not used for backup folder names, the smallest number is used for a new
backup folder name.
The oldest backup folder (date_number) is deleted and the number of the deleted folder is used for a new backup
folder name when unused number is no longer available due to such cases as the number of folders reached the
upper limit.
Specify a number (0 to 99) of the backup folder name.
When another folder with the same number exists, the target data is overwritten in execution unit without
*1
changing the folder name.
Operation
When the backup data with the same target module exists, the backup folder (start I/O number_station number)
is deleted before performing data backup.
When the backup data with the same target module and the same target station number exists, data backup is
performed after the backup folder (start I/O number_station number) is deleted.
When the backup data with the same target module and the same target station number exists, the information of
the backed up station sub-ID is added to the system file for iQ Sensor Solution backup/restoration.
When the backup data with the same target module, the same target station number, and the same target station
sub-ID number exists, the backup data (information of each station sub-ID) is deleted before performing data
backup.