MELSEC iQ-R series
The following table lists the special relays (SM) used for MELSEC iQ-R series.
Number
Name
SM606
SD memory card forced
disable instruction
SM1360
iQ Sensor Solution
backup/restoration
right-to-use request
SM1361
iQ Sensor Solution
backup request
SM1362
iQ Sensor Solution
backup normal
completion
SM1363
iQ Sensor Solution
backup abnormal
completion
SM1364
iQ Sensor Solution
restoration request
SM1365
iQ Sensor Solution
restoration normal
completion
SM1366
iQ Sensor Solution
restoration abnormal
completion
SM1367
iQ Sensor Solution
backup/restoration
cancellation request
Description
Details
OFF: Cancel instruction
When this relay is turned ON, the instruction that forcibly disables an
ON: Forced disable
SD memory card is issued. If any function accesses the SD memory
instruction
card, the disabling process does not start until the access is completed.
When this relay is turned OFF, the instruction that forcibly disables an
SD memory card is issued.
OFF to ON: Backup/
This relay requests acquiring/releasing a right to use for iQ Sensor
restoration right to use
Solution backup/restoration.
requested
At the timing when this relay turns OFF to ON, the relay requests a right
ON to OFF: Backup/
to use with the value specified to SD1360.
restoration right to use
This relay turns OFF when a right to use is acquired/released.
acquired/released
OFF to ON: Backup
This relay requests iQ Sensor Solution data backup.
requested
At the timing when this relay turns OFF to ON, the backup for the set
ON to OFF: Backup
device(s) is performed.
complete
This relay turns OFF when iQ Sensor Solution data backup is complete.
This relay turns ON to OFF when a right to use is acquired.
OFF: Other than normal
This relay turns ON when the iQ Sensor Solution data backup is
completion
complete normally.
ON: Backup complete
When iQ Sensor Solution data backup is compete with an error,
normally
SM1363 turns ON and this relay remains OFF.
This relay turns ON to OFF when a right to use is acquired or backup is
requested.
OFF: Other than error
This relay turns ON when iQ Sensor Solution data backup is complete
completion
with an error. The error code is stored to SD1376 or SD1377.
ON: Backup completed with
When iQ Sensor Solution data backup is compete normally, SM1362
error(s)
turns ON and this relay remains OFF.
This relay turns ON to OFF when a right to use is acquired or backup is
requested.
OFF to ON: Restoration
This relay requests the iQ Sensor Solution data restoration.
requested
At the timing when this relay turns OFF to ON, the restoration for the set
ON to OFF: Restoration
device(s) is performed.
complete
This relay turns OFF when iQ Sensor Solution data restoration is
complete.
This relay turns ON to OFF when a right to use is acquired.
OFF: Restoration is
This relay turns ON when iQ Sensor Solution data restoration is
complete abnormally
complete normally.
ON: Restoration complete
When iQ Sensor Solution data restoration is complete with an error,
normally
SM1366 turns ON and this relay remains OFF.
This relay turns ON to OFF when a right to use is acquired or a
restoration is requested.
OFF: Other than error
This relay turns ON when iQ Sensor Solution data restoration is
completion
complete with an error. The error code is stored to SD1376 or SD1377.
ON: Restoration completed
When iQ Sensor Solution data restoration is complete normally,
with error(s)
SM1365 turns ON and this relay remains OFF.
This relay turns ON to OFF when a right to use is acquired or a
restoration is requested.
OFF to ON: Backup/
This relay requests the cancellation of iQ Sensor Solution backup/
restoration
restoration.
cancellation requested
At the timing when this relay turns OFF to ON, iQ Sensor Solution
ON to OFF: Backup/
backup/restoration is cancelled.
restoration
This relay turns OFF when the cancellation of iQ Sensor Solution
cancellation complete
backup/restoration is complete.
This relay turns ON to OFF when a right to use is acquired or a backup/
restoration is requested.
Appendix 6 Special Relay (SM)/Special Register (SD) List
Set by
(setting
timing)
U
S (status
change)/U
S (status
change)/U
S (status
change)
S (status
change)
A
S (status
change)/U
S (status
change)
S (status
change)
S (status
change)/U