You have interconnected the "STO active" checkback signal. After STO has been selected,
the inverter signals "STO active" to the higher-level control.
Parameter
r9773.01
6.13.3.5

Setting the filter for fail-safe digital inputs

Requirement
You are online with STARTER or Startdrive online.
Procedure with STARTER
Proceed as follows to set the input filter and the simultaneity monitoring of the fail-safe digital
input:
1. Select the "Extended settings" button.
2. Set the debounce time for the F-DI input filter.
3. Set the discrepancy time for the simultaneity monitoring.
4. Close the screen form.
You have set the input filter and the simultaneity monitoring of the fail-safe digital input.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
Description
1 signal: STO is active in the drive
Advanced commissioning
6.13 Safe Torque Off (STO) safety function
201