Parameters
p2192
p2193 = 1
In applications with fans, pumps or compressors with the flow characteristic, the torque
follows the speed according to a specific characteristic. An insufficient torque for fans
indicates that the power transmission from the motor to the load is interrupted. For pumps,
insufficient torque can indicate a leakage or dry-running.
If the torque and speed lie in the impermissible range longer than time p2192, the inverter
reacts as specified in p2181.
For applications with pumps (p2193 = 4), the inverter detects the following states of the
driven load:
● Blocked
● Leakage
● Dry running
For applications with fans or compressors (p2193 = 5), the inverter detects the following
states of the driven load:
● Blocked
● Torn belt
The monitoring is not active below speed threshold 1 and above speed threshold 3.
When using the control mode "U/f control" (p1300 < 10), the "Blocking protection" function
becomes active when the current limit is reached.
Parameter
p2165
p2168
p2181
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
Description
Load monitoring delay time
Delay time for the message "Leave torque monitoring tolerance band"
Load monitoring configuration (factory setting: 1)
1: Monitoring torque and load drop
No-load monitoring (Page 270)
Description
Load monitoring blocking monitoring threshold, upper
Load monitoring blocking monitoring torque threshold
Load monitoring response
Advanced commissioning
6.24 Monitoring the driven load
273