Motor protection by calculating the temperature

The inverter calculates the motor temperature based on a thermal motor model.
The thermal motor model responds far faster to temperature increases than a temperature
sensor.
If you are using the thermal motor model together with a temperature sensor, e.g. a Pt1000,
then the inverter corrects the model based on the measured temperature.
Thermal motor model 2 for induction motors
The thermal motor model 2 for induction motors is a thermal 3-mass model, consisting of
stator core, stator winding and rotor. Thermal motor model 2 calculates the temperatures -
both in the rotor as well as in the stator winding.
Figure 6-60
Table 6- 44
Parameter Description
r0068
p0610
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
Description
2,
Alarm A07910 and fault F07011
12:
The inverter does not reduce the current limit.
Current limit [A]
Thermal motor model 2 for induction motors
Thermal motor model 2 for induction motors
CO: Absolute actual current value
Motor overtemperature response (factory setting: 12)
0:
Alarm A07012
The inverter does not reduce the current limit.
1:
Alarm A07012 and fault F07011
The inverter reduces the current limit.
2:
Alarm A07012 and fault F07011
The inverter does not reduce the current limit.