5.3.4
Defining additional requirements for the application
Minimum and maximum speed
● Minimum speed - factory setting 0 [rpm]
The minimum speed is the lowest speed of the motor independent of the speed setpoint.
A minimum speed is, for example, useful for fans or pumps.
● Maximum speed - factory setting 1500 [rpm]
The inverter limits the motor speed to this value.
Operate the inverter with the factory setting
For basic applications, you can try to operate the drive with a rated power < 18.5 kW without
any other commissioning steps. Check whether the control quality of the drive without
commissioning is adequate for the requirements of the application.
We recommend that you configure the drive with the precise motor data.
5.4
Quick commissioning
5.4.1
Motor data using p300 and p301
Preassigned motor data using p0300 and p0301
The SINAMICS G110M software has been configured to utilize the input of the motor data
using a motor code. There are two parameters associated with this function, they are p0300
(motor type) and p0301 (motor code).
When the SINAMICS G110M is ordered and delivered as a complete system, the motor data
is already correctly configured and does not require any adjustment.
When the SINAMICS G110M is ordered and delivered as separate items, the user must
install the system and enter the relevant motor data during basic commissioning.
When commissioning of the motor is required, there are two options available to the user:
Commissioning using motor codes
When commissioning using the motor codes, for example, in STARTER utilizing the "Expert
List", the follow steps should be performed:
1. Set p0010 = 1.
2. Set p0300 to 100 (1LE1 standard induction motor) or 177 (1LA7 standard induction
motor).
3. Enter the relevant motor code into p0301 as shown in the following table:
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
Commissioning
5.4 Quick commissioning
111