Operating the motor in a delta connection with 87 Hz characteristic
The motor only goes into field weakening above 87 Hz.
The higher motor power when operated with an 87 Hz characteristic has the following
disadvantages:
● The inverter must supply approximately 1.73x current. Select an inverter based on its
rated current - and not its rated power.
● The motor temperature increases more significantly than when operated with f ≤ 50 Hz.
● The motor must have windings that are approved for a voltage > rated voltage U
● As the fan impeller rotates faster, the motor has a higher noise level than operation with
f ≤ 50 Hz.
4.3.6

Cable protection

Cable protection for individual converters
If you individually protect an Inverter, then you must protect the Inverter feeder cable using a
fuse.
Table 4- 6
Rated power
0.37 kW
0.75 kW
1.1 kW
1.5 kW
2.2 kW
3 kW
4 kW
For additional information, please refer to Catalog D31at the following link:
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
Individual fuse protection
Power Module
6SL3517-1BE11-3AM0
6SL3517-1BE12-3AM0
6SL3517-1BE13-3AM0
6SL3517-1BE14-3AM0
6SL3517-1BE16-3AM0
6SL3517-1BE17-3AM0
6SL3517-1BE21-3AM0
4.3 Electrical Installation
In a delta connection, the motor is oper-
ated with a voltage and frequency above
its rated values. As a consequence, the
motor power is increased by a factor
√3 ≈ 1.73.
In the range f = 0 ... 87 Hz, the motor
can output its rated torque M
The maximum voltage U = 400 V is
available at a frequency of
f = √3 × 50 Hz ≈ 87 Hz.
Frame size
Fuse
FSA
10 A
FSA
10 A
FSA
10 A
FSA
10 A
FSB
20 A
FSB
20 A
FSB
20 A
Installation
.
N
.
N
3NA3803
3NA3803
3NA3803
3NA3803
3NA3807
3NA3807
3NA3807
79