10.3
SINAMICS G110M specifications
Power-dependent performance ratings
Note
UL certified Fuses must be used
UL certified Fuses must be used" it should state "In order that the system is in compliance
with UL requirements, UL listed class J fuses must be used. The fuse rating of these fuses
must be equal to or less that the ratings given in
Fuses (Page 63).
IP protection of the system
The Power Module and the Terminal Housing (which includes the Control Module) when fully
assembled and attach to the motor has an IP rating of IP65/66 depending on the version of
the Control Module.
Table 10- 1
PM240M, Frame Sizes A, Class A filter, 3 AC 380 V ... 480 V
Article No.
Rated / LO power
Rated / LO input current
Rated / LO Output current
HO power
HO input current
HO output current
Fuse
Power losses
Required cooling air flow
Cross section of line and motor cable
Tightening torque for line and motor cable
Weight
Table 10- 2
PM240M, Frame Sizes A, Class A filter, 3 AC 380 V ... 480 V
Article No.
Rated / LO power
Rated / LO input current
Rated / LO Output current
HO power
HO input current
HO output current
Fuse
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
6SL3517-...
...1BE11-3AM0
0.37 kW
1.3 A
1.3 A
0.37 kW
1.3 A
1.3 A
10 A, class J, CC
0.012 kW
4.8 l/s
1 ... 2.5 mm
18 ... 14 AWG
0.5 Nm / 4 lbf in
2.1 kg
6SL3517-...
...1BE14-3AM0
1.5 kW
3.6 A
4.1 A
1,5kW
3.6 A
4.1 A
10 A, class J, CC
10.3 SINAMICS G110M specifications
Table 4-2 Rated Output, Input and
...1BE12-3AM0
0.75 kW
2.0 A
2.2 A
0.75 kW
2.0 A
2.2 A
10 A, class J, CC
0.014 kW
4.8 l/s
1 ... 2.5 mm
2
2
18 ... 14 AWG
0.5 Nm / 4 lbf in
2.1 kg
Technical data
...1BE13-3AM0
1.1 kW
2.8 A
3.1 A
1,1 kW
2.8 A
3.1 A
10 A, class J, CC
0.2 kW
4.8 l/s
1 ... 2.5 mm
2
18 ... 14 AWG
0.5 Nm / 4 lbf in
2.1 kg