Setting The Filter For Fail-Safe Digital Inputs - Siemens SINAMICS G120C USS/MB Operating Instructions Manual

Sinamics g120c series low voltage converter built-in units with frame sizes aa - f
Hide thumbs Also See for SINAMICS G120C USS/MB:
Table of Contents

Advertisement

6.15.2.4

Setting the filter for fail-safe digital inputs

Requirement
You are online with STARTER or Startdrive online.
Procedure with STARTER
Proceed as follows to set the input filter and the simultaneity monitoring of the fail-safe digital
input:
1. Select the "Extended settings" button.
2. Set the debounce time for the F-DI input filter.
3. Set the discrepancy time for the simultaneity monitoring.
4. Close the screen form.
You have set the input filter and the simultaneity monitoring of the fail-safe digital input.
Procedure with Startdrive
Proceed as follows to set the input filter and the simultaneity monitoring of the fail-safe digital
input:
1. Navigate to the filter settings.
2. Set the debounce time for the F-DI input filter.
3. Set the discrepancy time for the simultaneity monitoring.
You have set the input filter and the simultaneity monitoring of the fail-safe digital input.
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
Advanced commissioning
6.15 Safe Torque Off (STO) safety function
223

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120c dpSinamics g120c pn

Table of Contents