Advanced settings
You can debounce the digital input signal using parameter p0724.
For more information, see the parameter list and the function block diagrams 2210 ff of the
List Manual.
Analog inputs as digital inputs
6.2.2.2

Fail-safe digital input

This manual describes the STO safety function with control using a fail-safe input. Additional
safety functions, additional fail-safe digital inputs, the fail-safe digital output of the converter
and the control of the safety functions using PROFIsafe are described in the "Safety
Integrated" Function Manual.
Defining a fail-safe digital input
If you use the STO safety function, then you must configure this during the basic
commissioning for a fail-safe digital input, e.g. with p0015 = 2.
The converter combines digital inputs DI 4 and DI 5 to form a fail-safe digital input.
Fail-safe digital input
Converter with control units CU240D-2
Operating Instructions, 07/2016, FW V4.7 SP6, A5E34262100B AD
Connections and cables (Page 49)
When required, you can use the analog inputs as
additional digital inputs.
Function
You must enable STO to select the STO safety function (Basic
Safety) via FDI 0.
Safe Torque Off (STO) safety function (Page 217)
Advanced commissioning
6.2 Inverter control
113