Advanced commissioning
6.3 Adapt the default setting of the inputs and outputs
Table 6- 5
Parameter
p0757
p0758
p0759
p0760
p0761
Defining the analog input function
You define the analog input function by interconnecting a connector input of your choice with
parameter p0755 . Parameter p0755 is assigned to the particular analog input via its index,
e.g. parameter p0755[0] is assigned to analog input 0.
Table 6- 6
CI
p1070 Main setpoint
p1075 Supplementary setpoint
p1503 Torque setpoint
p1511 Supplementary torque 1
A complete list of the connector inputs is provided in the List Manual.
Defining the analog input function - example
Advanced settings
Signal smoothing
When required, you can smooth the signal, which you read-in via an analog input, using
parameter p0753.
You can find more information in the parameter list and in function diagram 2251 of the List
Manual.
148
Parameters for the scaling characteristic and wire break monitoring
Description
x-coordinate of 1st characteristic point [V]
y coordinate of the 1st characteristic point [% of p200x]
p200x are the parameters of the reference variables, e.g. p2000 is the reference
speed.
x-coordinate of 2nd characteristic point [V]
y-coordinate of 2nd characteristic point [% of p200x]
Wire breakage monitoring response threshold
Connector inputs (CI) of the inverter (selection)
Significance
Manuals for your converter (Page 372)
CI
Significance
p1522 Torque limit, upper
p2253 Technology controller setpoint 1
p2264 Technology controller actual value
In order to use the analog input AI 0 as the source for
the supplementary setpoint, you have to set
p1075 = 755[0].
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH