Installation
4.2 System Installation
4. Connect the motor earth cable to the Terminal Housing
5. Connect the Terminal Housing motor terminals to the motor
6. Connect the EM brake cables
52
1. Feed the motor earth cable through the Terminal Housing.
2. Secure the motor earth cable to the Terminal Housing
earthing post (1.5 Nm).
1. Connect the U, V and W terminals of the Terminal Housing
to U1, V1 and W1 terminals of the motor.
2. Ensure that the cables are routed as to not obstruct access
to other components of the system.
Note:
• The motor terminals on the Terminal Housing are delivered
pre-wired at the correct length for easy fitting.
• The mains supply and motor terminals have a maximum
torque of 0.8 Nm.
The motor terminals on the Terminal Housing are delivered
pre-wired at the correct length for easy fitting.The mains supply
and motor terminals have a maximum torque of 0.8 Nm.
1. Feed the external EM brake cable through the EM brake
cable gland.
2. Connect the external EM brake cable to the EM brake
terminal block.
3. Ensure that the plastic insulation sleeve is fitted correctly to
the EM brake terminal block (which is part of the
accessories supplied with the product).
4. Tighten the cable gland to secure the cable in place.
Notes:
• Only a 180 Vdc EM brake can be used.
• If a brake is not used the cable entry must be sealed with a
blanking plug to ensure the IP65 rating of the system is
maintained.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH