Siemens Sinamics G110M Operating Instructions Manual page 243

Sinamics series distributed converter for simogear geared motors
Hide thumbs Also See for Sinamics G110M:
Table of Contents

Advertisement

Figure 6-50
When droop is active, the ramp-function generators of all of the coupled drives must be set
to have identical ramp-up and ramp-down times as well as rounding-off.
Par.
r1482
p1488
p1489
r1490
p1492
After selecting application class "Dynamic Drive Control", droop is no longer possible.
You can find additional information in the List Manual, function block diagram 6030.
Special settings for a pulling load
For a pulling load, e.g. a hoisting gear, a permanent force is exerted on the motor, even
when the motor is stationary.
For a pulling load, we recommend that you use vector control with an encoder.
If you use encoderless vector control with a pulling load, then the following settings are
required:
● Set the following parameters:
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
Effect of droop in the speed controller
Explanation
Speed controller I torque output
Droop input source (factory setting: 0)
0: Droop feedback not connected
1: Droop from the torque setpoint
2: Droop from the speed control output
3: Droop from the integral output, speed controller
Droop feedback scaling (factory setting: 0.05)
A value of 0.05 means: At the rated motor torque, the inverter reduces the speed by 5% of
the rated motor speed.
Droop feedback speed reduction
Droop feedback enable (factory setting: 0)
Par.
Explanation
p1750
Motor model configuration
Bit 07 = 1
Use speed switchover limits that are less sensitive to external effects
Advanced commissioning
6.17 Motor control
243

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents