Advertisement

Commissioning
5.4 Quick commissioning
Motor identification:
● [1]: Recommended setting. Measure the motor data at standstill and with the motor
rotating. The inverter switches off the motor after the motor data identification has been
completed.
● [2]: Measure the motor data at standstill. The inverter switches off the motor after the
motor data identification has been completed.
Recommended setting for the following cases:
– You have selected "Speed control" as control mode, however the motor cannot freely
– You have set "U/f control" as control mode.
● [3]: Measure the motor data while it is rotating. The inverter switches off the motor after
the motor data identification has been completed.
● [11]: The same setting as [1]. The motor accelerates to the currently set setpoint after the
motor data identification.
● [12]: The same setting as [2]. The motor accelerates to the currently set setpoint after the
motor data identification.
Calculating the motor parameters: Select "Complete calculation".
8.
9. Set the check mark for "RAM to ROM (save data in
You have entered all of the data that is necessary for the basic commissioning of your
inverter.
132
rotate, e.g. for mechanically limited traversing sections.
Moment of inertia estimator (Page 246)
We recommend the
setting "Calculate motor
data only".
the drive)" in order to save your data in the inverter
so that it is not lost when the power fails.
Exit basic commissioning.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH