Advanced commissioning
6.24 Monitoring the driven load
For more information, see the List Manual (the parameter list and function diagram 8013).
6.24.3

Torque monitoring

In applications with fans, pumps or compressors with the flow characteristic, the torque
follows the speed according to a specific characteristic. An insufficient torque for fans
indicates that the power transmission from the motor to the load is interrupted. For pumps,
insufficient torque can indicate a leakage or dry-running.
The inverter monitors the torque based on the envelope curve depending on the speed
against a lower and upper torque.
If the torque lies in the impermissible range longer than time p2192, the inverter reacts as
specified in p2181.
The monitoring is not active below speed threshold 1 and above speed threshold 3.
Parameters
p2181
p2182
p2183
p2184
p2185
p2186
p2187
p2188
p2189
p2190
272
Description
Load monitoring response
1: A07920 for torque too low
2: A07921 for torque too high
3: A07922 for torque outside tolerance
4: F07923 for torque too low
5: F07924 for torque too high
6: F07925 for torque outside tolerance
Load monitoring speed threshold 1
Load monitoring speed threshold 2
Load monitoring speed threshold 3
Load monitoring torque threshold 1, upper
Load monitoring torque threshold 1, lower
Load monitoring torque threshold 2, upper
Load monitoring torque threshold 2, lower
Load monitoring torque threshold 3, upper
Load monitoring torque threshold 3, lower
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
The inverter interpolates
linearly between characteris-
tic points.