Siemens Sinamics G110M Operating Instructions Manual page 181

Sinamics series distributed converter for simogear geared motors
Hide thumbs Also See for Sinamics G110M:
Table of Contents

Advertisement

Figure 6-17
The load is then slowed down and stopped.
Figure 6-18
There are two sensors on the conveyor section, so that the Quick Stop function can stop the
conveyor section in either direction when a load is detected.
How does it work?
The Quick Stop function is configured using BICO parameters and they are explained in the
table below.
Table 6- 19
Quick Stop parameters
Parameter
Description
P0881
Quick Stop function Input 1 is ON
P0882
Quick Stop function Input 2 is ON
P0883
Quick Stop override
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
Conveyor example 2
Conveyor example 3
Remarks
Allows Quick Stop source 1 command to be selected using
BICO. The signal is expected to be active low (default setting
P0886 = 2).
Allows Quick Stop source 2 command to be selected using
BICO. The signal is expected to be active low (default setting
(P0886 = 2).
Allows Quick Stop override command source to be selected
using BICO. The signal is expected to be active high.
Advanced commissioning
6.8 Quick Stop function
181