Prepare Commissioning - Siemens Sinamics G110M Operating Instructions Manual

Sinamics series distributed converter for simogear geared motors
Hide thumbs Also See for Sinamics G110M:
Table of Contents

Advertisement

Internet: STARTER download
1)
(http://support.automation.siemens.com/WW/view/en/26233208)
Internet:StartDrive download
2)
(http://support.automation.siemens.com/WW/view/en/68034568)
5.3

Prepare commissioning

Overview
Before starting commissioning, you must know the answer to the following questions:
Inverter
● What are the data specifications of my inverter?
→ Figure 3-1 Identifying the components of the system (Page 28).
● How is the inverter integrated in the higher-level control system?
→ Via the terminals or the fieldbus interface?
Saving non-standard motor data to EEPROM
When performing a factory reset on the converter, all parameter data is reset to the factory
default settings. The default settings for the motor data assumes you are using a Siemens
standard 4-pole motor.
If you are not using a Siemens standard 4-pole motor with a motor which has the same
rating as the converter, for example, a 1.5 kW converter and a 1.5 kW motor, then your
application will not work correctly after a factory reset.
When using a non-standard motor, the motor data must be saved to the converter's non-
volatile memory (EEPROM), this will ensure that even after a factory reset, your unique
motor data will not be overwritten and will remain intact.
To save your unique motor data to the converter's EEPROM, the following procedure should
be performed.
1. Commission the converter using the STARTER Quick Commissioning wizard.
2. Ensure that a motor data identification is performed, at the completion of the
commissioning procedure.
3. Perform a "Copy from RAM to ROM".
4. Set parameter p0726 to 1.
5. When the motor data save is complete, parameter p0726 will be set back to 0.
6. The motor data is saved to the converter's EEPROM.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
Commissioning
5.3 Prepare commissioning
105

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents