Siemens Sinamics G110M Operating Instructions Manual page 77

Sinamics series distributed converter for simogear geared motors
Hide thumbs Also See for Sinamics G110M:
Table of Contents

Advertisement

I/O terminal diagram - all varaints
The maximum combined current for all digital inputs is 200 mA and the maximum combined
current for all digital outputs is 500 mA.
Terminal housing mains supply connections
Type: HAN Q4/2 (Input and
Output), 3 AC 380 V (-10%)
... 480 V (+10%)
Important:
The pinouts refer to the ac-
tual connectors on the ter-
minal housing.
The terminal designation
X1/3 is used because the
mains input and output can
be swapped around depend-
ing on which side of the
terminal housing the CPI is
mounted.
Internal motor and power connection
The internal motor and power connections on the G110M system are located inside the
Control Unit and motor housing. The connections are shown in the following figure.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
Installation
4.3 Electrical Installation
M12 connector, 5 Pole, female
Specification:
PNP, SIMATIC-compatible,
low <5 V, high > 10 V maxi-
mum, input voltage 30 V.
The Control Module (CM) is
fitted inside the terminal hous-
ing and is connected by ribbon
cable to the CPI.
M12 connector, 8 Pole, female
X10 for USS, Profibus and
Profinet,
X15 for AS-i
77

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents