Advertisement

For more information, see the parameter list and the function block diagrams 2210 ff of the
List Manual.
Analog inputs as digital inputs
6.3.2

Digital outputs

Changing the function of the digital output
Table 6- 4
0
r0052.0
r0052.1
r0052.2
r0052.3
r0052.4
r0052.5
r0052.6
r0052.7
r0052.8
A complete list of the binector outputs is provided in the List Manual.
Changing the function of a digital output - example
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
Binector outputs of the inverter (selection)
Deactivating digital output
Drive ready
Drive ready for operation
Drive running
Drive fault active
OFF2 active
OFF3 active
Closing lockout active
Drive alarm active
Setpoint/actual value discrepancy
6.3 Adapt the default setting of the inputs and outputs
When required, you can use the analog inputs as
additional digital inputs.
Interconnect the digital output with a binector output
of your choice.
Interconnecting signals in the inverter
(Page 359)
Binector outputs are marked with "BO" in the pa-
rameter list of the List Manual.
r0052.9
Process data control
r0052.10
f_actual >= p1082 (f_max)
r0052.11
Alarm: Motor current/torque limit
r0052.12
Brake active
r0052.13
Motor overload
r0052.14
Motor CW rotation
r0052.15
Inverter overload
r0053.0
DC braking active
r0053.2
f_actual > p1080 (f_min)
r0053.6
f_actual ≥ setpoint (f_setpoint)
In order to output the fault message over the digital
output DO 1, you have to connect the DO 1 with the
fault message: Set p0731 = 52.3.
Advanced commissioning
145