Table 1-32
Low-voltage 37 kVA Three Phase PDUs for North America, South
America, Japan and Taiwan (2 PDUs per Rack)
Option
Voltage
Frequency
Current
Power rating
Output current
Outlets
Outlet groups
Group protection (UL489 1-pole circuit
breaker)
Data center receptacle
The following are needed to connect an Oracle Exadata system to a low-voltage three-
phase power source:
3 power cords for each PDU, 60 amperes at 190 - 220 VAC three-phase
3 receptacles to connect the PDUs to 2 IEC 60309 60A 4-pin 250VAC 3ph IP67
data center receptacles
Figure 1-2
(page 1-37) shows the low-voltage 37 kVA single phase PDU power
connector for North America, South America, Japan and Taiwan.
Table 1-33
(page 1-42) lists the requirements for 37 kVA high-voltage three-phase
PDUs for Oracle Exadata Database Machine X6-8, X5-8, and X4-8 with more than four
database servers. There are two PDUs per rack. The following specifications are per
PDU.
Table 1-33
High-voltage 37 kVA Three Phase PDUs for Europe, the Middle East
and Africa (EMEA), and Asia Pacific (APAC), except for Japan and Taiwan (2
PDUs per Rack)
Option
Voltage
Frequency
Current
Power rating
Output current
Outlets
Outlet groups
Group protection (UL489 1-pole circuit
breaker)
Data center receptacle
Electrical Power Requirements
Requirement, per PDU
200 - 208 VAC
50/60 Hz
34.6 A maximum per phase
37 kVA
180 A (9 x 20 A)
44 C13 and 9 C19
6
20 A
IEC 309-3P4W-IP67 plugs
Requirement, per PDU
220/380 - 240/415 VAC
50/60 Hz
18 A maximum per phase
37 kVA
163 A (9 x 18.1 A)
45 C13 and 9 C19
6
20A
IEC 309-4P5W-IP44
Chapter 1
1-42