Table 1-3
Environmental Requirements for Oracle Exadata Database Machine
X4-2
Environmental
Oracle Exadata
Component
Database
Machine X4-2
Full Rack
Weight
852.8 kg (1880
lbs)
See Also:
"Flooring
Requirements
(page 1-34)"
Acoustic levels
93 db(A)
Power
High
performance
See Also:
drives
"Electrical Power
Requirements
Maximum:
(page 1-34)"
12.4 kVA
Typical: 8.7
kVA (varies
based on
application
load)
High
capacity
drives
Maximum:
11.4 kVA
Typical: 8.1
kVA (varies
based on
application
load)
General Environmental Requirements
Oracle Exadata
Oracle Exadata
Database
Database
Machine X4-2
Machine X4-2
Half Rack
Quarter Rack
525.3 kg (1158
365.6 kg (806
lbs)
lbs)
89 db(A)
85 db(A)
High
High
performance
performance
drives
drives
Maximum:
Maximum:
6.8 kVA
3.4 kVA
Typical: 4.8
Typical: 2.5
kVA (varies
kVA (varies
based on
based on
application
application
load)
load)
High
High
capacity
capacity
drives
drives
Maximum:
Maximum:
6.3 kVA
3.2 kVA
Typical: 4.4
Typical: 2.3
kVA (varies
kVA (varies
based on
based on
application
application
load)
load)
Chapter 1
Oracle Exadata
Database
Machine X4-2
Eighth Rack
365.6 kg (806
lbs)
85 db(A)
High
performance
drives
Maximum:
3.1 kVA
Typical: 2.2
kVA (varies
based on
application
load)
High
capacity
drives
Maximum:
2.9 kVA
Typical: 2.1
kVA (varies
based on
application
load)