Table 1-6
(Cont.) Environmental Requirements for Oracle Exadata Database
Machine X3-2
Environmental
Oracle Exadata
Component
Database
Machine X3-2
Full Rack
Cooling
High
performance
See Also:
drives
"Temperature
and Humidity
Maximum:
Requirements
40,600 BTU/
(page 1-44)",
hour (42,800
and
"Ventilation
kJ/hour)
and Cooling
Typical:
Requirements
28,700 BTU/
(page 1-45)"
hour (30,300
kJ/hour)
High
capacity
drives
Maximum:
37,200 BTU/
hour (39,250
kJ/hour)
Typical:
26,000 BTU/
hour (27,400
kJ/hour)
Air flow front-to-
High
back (subject to
performance
actual data
drives
center
Maximum:
environment)
Approximatel
See Also:
y 1,900 CFM
"Temperature
Typical:
and Humidity
Approximatel
Requirements
y 1,350 CFM
(page 1-44)",
High
and
"Ventilation
capacity
and Cooling
drives
Requirements
Maximum:
(page 1-45)"
Approximatel
y 1,700 CFM
Typical:
Approximatel
y 1,200 CFM
General Environmental Requirements
Oracle Exadata
Oracle Exadata
Database
Database
Machine X3-2
Machine X3-2
Half Rack
Quarter Rack
High
High
performance
performance
drives
drives
Maximum:
Maximum:
22,200 BTU/
10,900 BTU/
hour (23,400
hour (11,500
kJ/hour)
kJ/hour)
Typical:
Typical:
15,700 BTU/
7,850 BTU/
hour (16,600
hour (8,300
kJ/hour)
kJ/hour)
High
High
capacity
capacity
drives
drives
Maximum:
Maximum:
20,500 BTU/
10,200 BTU/
hour (21,600
hour (10,800
kJ/hour)
kJ/hour)
Typical:
Typical:
14,300 BTU/
7,200 BTU/
hour (15,100
hour (7,600
kJ/hour)
kJ/hour)
High
High
performance
performance
drives
drives
Maximum:
Maximum:
Approximatel
Approximatel
y 1,050 CFM
y 500 CFM
Typical:
Typical:
Approximatel
Approximatel
y 750 CFM
y 375 CFM
High
High
capacity
capacity
drives
drives
Maximum:
Maximum:
Approximatel
Approximatel
y 950 CFM
y 470 CFM
Typical:
Typical:
Approximatel
Approximatel
y 670 CFM
y 330 CFM
Chapter 1
Oracle Exadata
Database
Machine Eighth
Rack
High
performance
drives
Maximum:
9,900 BTU/
hour (10,500
kJ/hour)
Typical:
6,800 BTU/
hour (7,200
kJ/hour)
High
capacity
drives
Maximum:
9,200 BTU/
hour (9,700
kJ/hour)
Typical:
6,500 BTU/
hour (6,850
kJ/hour)
High
performance
drives
Maximum:
Approximatel
y 460 CFM
Typical:
Approximatel
y 325 CFM
High
capacity
drives
Maximum:
Approximatel
y 425 CFM
Typical:
Approximatel
y 300 CFM
1-13